Wiring (Mv100 Only); Operation; Settings And Adjustments - Honeywell Braukmann T100A Product Data

Table of Contents

Advertisement

MV100 ELECTRIC CONTROLLERS T100, T200 THERMOSTATIC CONTROLLERS AND V100 RADIATOR VALVES
Location and Mounting
Because these controls are thermostats that have sensors
that measure air temperature in the immediate vicinity, it is
critical to select an appropriate installation location.
These devices are adversely affected by radiant heat, solar
heat or airflow obstructions such as curtains or enclosures. Two
essential considerations for choosing the correct controller/
valve body combination for a particular installation are:
— Adequate dimensional clearances.
— Proper sensor positioning.
IMPORTANT
Install built-in sensor type controllers in a horizontal
position to prevent air warmed by the hot valve body
from influencing the sensor.
NOTE: The most common misapplication of these valves
and controllers is the use of a horizontal-body valve
(V100E) with a direct-mount controller (T100A,M or
T200A). See Fig. 17.
INCORRECT
Fig. 17. Horizontal-body V100 application.
Install controllers with external sensors in any position. The
sensor can easily be mounted in a position to measure and
control the room air temperature.
NOTE: When temperature of medium exceeds 190°F
(88°C), mount the MV100 horizontally.

WIRING (MV100 ONLY)

Wire the MV100 according to Fig. 18.
CAUTION
Equipment Damage Hazard.
Can short equipment circuitry.
Disconnect all power supplies before installation.
CAUTION
Equipment Damage Hazard.
Connecting improper voltage can damage the
device beyond repair.
Connect only 24 Vac or 24 Vdc to the MV100.
62-3048—1
CORRECT
M16272
8
MV100
END
SWITCH
RED
RED
2
YELLOW
PTC
RESISTANCE
YELLOW
HEATER
3
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
2
NORMALLY OPEN END SWITCH CLOSES WHEN MV100 IS POWERED.
3
SUGGESTED HEAT ANTICIPATOR SETTING IS 0.35A.
Fig. 18. MV100 internal schematic
and wiring connections.

OPERATION

The T100 and MV100 Controllers contain temperature-
sensitive capsules that expand or contract in reaction to
temperature changes.
— When the capsule expands, pressure from the expanding
material closes the valve, preventing flow through the
radiation unit.
— When the capsule contracts, the valve opens and flow
resumes through the radiation unit.
T100
The T100 temperature-sensitive capsule expands when the
temperature rises above the setpoint.
MV100
When signalled by the thermostat, an electric element in the
MV100 heats the capsule causing it to expand.
NOTE: For normally open MV100 models, the capsule cools
when signalled by the thermostat.

SETTINGS AND ADJUSTMENTS

When installation is complete, rotate the setpoint dial to the
desired setting.
NOTE: The setpoint varies with the location of the sensor. A
floor level sensor controls at a setpoint different from
the wall level sensor.
Normally, correction of an overheating or underheating
condition requires only small changes. See Table 5 for dial
markings and corresponding temperature settings. After
changing the setting, allow the valve at least 30 minutes to
stabilize.
TO CIRCULATOR
PUMP MULTIZONE
PANEL OR BURNER
RELAY
L1
(HOT)
L2
T810/T822
1
M12947A

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents