Lennox LGT156H Installation Instructions Manual page 30

Table of Contents

Advertisement

180 NORMAL OPERATING PRESSURES - REHEAT - ALL-ALUMINUM COIL - 581087-01
65 F
Suct
Disc
(psig)
(psig)
100
237
107
239
Circuit 1
122
245
136
254
105
249
113
251
Circuit 2
129
258
145
271
113
251
121
255
Circuit 3
139
264
155
278
180 CHARGING CURVE CIRCUIT 1 - REHEAT - ALL-ALUMINUM COIL - 581088-01
120
110
100
90
80
70
60
100
110
LGT/LCT156, 180, 210, 240, 300
Outdoor Coil Entering Air Temperature
75 F
85 F
Suct
Disc
Suct
(psig)
(psig)
(psig)
102
271
104
110
273
113
126
279
129
141
287
145
106
288
108
115
288
117
132
293
135
149
305
153
115
290
116
124
293
126
141
303
144
159
316
162
120
Suction Pressure (psig)
Page 30
TABLE 7
95 F
Disc
Suct
Disc
(psig)
(psig)
(psig)
312
106
357
313
115
359
318
133
363
326
149
371
333
109
385
332
119
384
336
138
385
345
157
393
333
118
382
336
128
385
346
147
394
359
166
407
65°
130
140
105 F
115 F
Suct
Disc
Suct
(psig)
(psig)
(psig)
108
409
109
117
410
119
136
414
138
153
421
157
111
444
112
121
442
123
141
441
144
161
447
164
120
435
122
130
438
132
150
447
153
169
459
173
Outdoor Temperature (°F)
105°
95°
85°
75°
150
Disc
(psig)
465
466
470
476
510
507
504
508
494
496
504
517
115°
160

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents