2- Add or remove charge in increments. Allow the
system to stabilize each time refrigerant is added or
removed.
3- Continue
the
process
temperature
agrees
temperature. Do not go below the target liquid
temperature when adjusting charge. Note that
suction pressure can change as charge is adjusted.
until
measured
liquid
with
the
target
liquid
4- Example: At 95°F outdoor ambient and a measured
suction pressure of 130psig, the target liquid
temperature is 98°F. For a measured liquid
temperature of 106°F, add charge in increments until
measured liquid temperature agrees with the target
liquid temperature.
Page 23
508288-01
9/2022