156 NORMAL OPERATING PRESSURES - REHEAT - ALL-ALUMINUM COIL - 581083-01
65 F
Suct
Disc
(psig)
(psig)
113
245
118
247
Circuit 1
128
255
137
264
112
260
116
262
Circuit 2
125
269
133
280
156 CHARGING CURVE CIRCUIT 1 - REHEAT - ALL-ALUMINUM COIL - 581084-01
120
110
100
90
80
70
60
110
120
LGT/LCT156, 180, 210, 240, 300
Outdoor Coil Entering Air Temperature
75 F
85 F
Suct
Disc
Suct
(psig)
(psig)
(psig)
116
282
119
123
284
126
135
291
140
145
300
153
115
298
118
121
300
125
132
307
138
141
318
149
130
Suction Pressure (psig)
Page 26
TABLE 5
95 F
Disc
Suct
Disc
(psig)
(psig)
(psig)
324
121
372
326
129
374
333
145
380
342
160
389
342
120
392
344
128
393
350
143
399
361
157
409
75°
65°
140
150
105 F
115 F
Suct
Disc
Suct
(psig)
(psig)
(psig)
122
425
122
131
427
132
149
433
153
166
442
172
122
447
123
131
449
133
148
454
152
164
464
170
Outdoor Temperature (°F)
105°
95°
85°
160
170
Disc
(psig)
484
486
492
500
508
510
515
524
115°