Function:
You can specify the discrepancy time for each channel pair.
Behavior while discrepancy time is running:
While the configured discrepancy time is running inside the module, the affected input channels
supply either the last valid value or "0" to the safety program in the F-CPU, depending on the
configured discrepancy behavior.
Behavior after expiration of the discrepancy time:
If after expiration of the configured discrepancy time the input signals are still different (when
testing for non-equivalence: input signals are still the same), e.g. due to a sensor wire break, a
discrepancy error is detected and the diagnostics message "Discrepancy error" is generated
along with information on the faulty channels.
Reintegration after discrepancy error
Requirement:
You have configured the following:
• "Sensor evaluation": "1oo2 evaluation, equivalent" or "1oo2 evaluation, non-equivalent"
Function:
You use this parameter to specify when a discrepancy error is regarded as corrected, thus
enabling reintegration of the affected input channels. You have the following parameter
assignment options:
• "Test 0-Signal necessary"
• "Test 0-Signal not necessary"
Option "Test 0-Signal necessary":
If you have configured "Test 0-Signal necessary", a discrepancy error is not regarded as corrected
until a 0-signal is present again at both of the affected input channels.
If you are using non-equivalent sensors, i.e. "Sensor evaluation" is set to "1oo2 evaluation, non-
equivalent", the result of the channel pair must be "0" again.
Option "Test 0-Signal not necessary":
If you have configured "Test 0-Signal not necessary", a discrepancy error is regarded as corrected
when a discrepancy is no longer present at both of the affected input channels.
5.2.5

Parameters of the channels

Channel activated
Specifies whether a channel is activated or deactivated.
F-DI 16x24VDC HA
Equipment Manual, 08/2021, A5E45647528-AD
Parameters/address space
5.2 Description of parameters
29

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simatic f-di 16x24vdc ha

Table of Contents