PROFIsafe addresses have to be unique for the station
• Station-wide uniqueness:
• Cross-station uniqueness:
• Verification following a change:
For Ethernet subnets and mixed configurations of PROFIBUS and Ethernet subnets, the
following also applies:
The combination of F-source address and F-destination address of all F-I/O modules only has to
be unique throughout the Ethernet subnet including all lower-level PROFIBUS subnets, under
the exclusion of cyclic PROFINET IO communication between Ethernet subnets.
(FDIW-002)
F_monitoring time (ms)
With this parameter you set the monitoring time for safety-related communication between the
F-CPU and F-I/O (PROFIsafe monitoring time) for safety operation.
The parameter is assigned a default value, but you can change it.
The configured F-monitoring time influences the response time of the system to a system error.
For this reason, the selected time must be as short as possible, but still long enough to prevent
timeouts when no error is occurring.
5.2.2

Cross-channel parameters

Distinction between "Cross-channel parameters" / "Channel parameters":
F-DI 16x24VDC HA
Equipment Manual, 08/2021, A5E45647528-AD
WARNING
Fail-safe I/O modules of the ET 200SP HA are uniquely addressed station-wide by a
combination of F-source address (PROFIsafe basic address of the assigned F-CPU) and F-
destination address. The F-system itself ensures that the F-destination addresses of all F-I/O
modules within the assigned F-CPU are unique.
To guarantee uniqueness across stations, you must verify that the PROFIsafe addresses
("F_source_address" + "F_destination_address") of the F-I/O modules are unique across
stations.
Because the F-source address "F_source_address" of the PROFIsafe address of the F-CPU is
automatically set to "1", you can only change the preset address "F_destination_address" for
F-I/O modules of the ET 200SP HA.
Note that the PROFIsafe address of the F-I/O module must be unique across all stations!
Parameters/address space
5.2 Description of parameters
25