Guide Specifications - Carrier Comfort 59SC5B Product Data

95 single-stage, 4-way multipoise, condensing gas furnace
Table of Contents

Advertisement

59SC5B: Product Data

GUIDE SPECIFICATIONS

General
System Description
Furnish a ______________________ 4-way multipoise gas-fired
condensing furnace for use with natural gas or propane (factory-
authorized conversion kit required for propane).
Quality Assurance
Unit will be designed, tested and constructed to the current ANSI Z
21.47/CSA 2.3 design standard for gas-fired central furnaces.
Unit will be third party certified by CSA to the current ANSI Z
21.47/CSA 2.3 design standard for gas-fired central furnaces. Unit will
carry the CSA Blue StarR and Blue FlameR labels. Unit efficiency
testing will be performed per the current DOE test procedure as listed in
the Federal Register.
Unit will be certified for capacity and efficiency and listed in the latest
AHRI Consumer's Directory of Certified Efficiency Ratings.
Unit will carry the current Federal Trade Commission Energy Guide
efficiency label.
Delivery, Storage, and Handling
Unit will be shipped as single package only and is stored and handled per
unit manufacturer's recommendations.
Warranty (for inclusion by specifying engineer)
U.S. and Canada only. Warranty certificate available upon request.
Equipment
Blower Wheel and ECM Blower Motor
Galvanized blower wheel shall be centrifugal type, statically and
dynamically balanced. Blower motor of ECM type shall be permanently
lubricated with sealed ball bearings, of _______hp, and have multiple
speeds from 600-1200 RPM operating only when 24-VAC motor inputs
are provided. Blower motor shall be direct drive and soft mounted to the
blower housing to reduce vibration transmission.
Filters
Furnace shall have reusable-type filters. Filter shall be ______ in. (mm)
X ________ in. (mm). An accessory highly efficient Media Filter is
available as an option. _____________ Media Filter.
Casing
Casing shall be of .030 in. thickness minimum, pre-painted steel.
Draft Inducer Motor
Draft inducer motor shall be single-speed PSC design.
Primary Heat Exchangers
Primary heat exchangers shall be 3-Pass corrosion-resistant aluminized
steel of fold-and-crimp sectional design and applied operating under
negative pressure.
Secondary Heat Exchangers
Secondary heat exchangers shall be of a stainless steel flow-through of
fin-and-tube design and applied operating under negative pressure.
Controls
Controls shall include a micro-processor-based integrated electronic
control board with at least 16 service troubleshooting codes displayed
via diagnostic flashing LED light on the control, a self-test feature that
checks all major functions of the furnace, and a replaceable
automotive-type circuit protection fuse. Multiple operational settings
available, including blower speeds for heating and cooling.
Operating Characteristics
Heating
capacity
shall
be
______________ Btuh output capacity.
Fuel Gas Efficiency shall be __________AFUE.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
_________________
Btuh
Air delivery shall be ________________ cfm minimum at 0.50 in. W.C.
external static pressure.
Dimensions shall be: depth_________in. (mm); width __________in.
(mm); height___________in. (mm) (casing only). Height shall
be_________in. (mm) with A/C coil and _________________in. (mm)
overall with plenum.
Electrical Requirements
Electrical supply shall be 115 volts, 60 Hz, single-phase (nominal).
Minimum wire size shall be ________AWG; maximum fuse size of
HACR-type designated circuit breaker shall be _________ amps.
Special Features
Refer to section of the product data identifying accessories and
descriptions for specific features and available enhancements.
input;
17

Advertisement

Table of Contents
loading

Table of Contents