Field setting mode
[DHW Tank water temperature thermo on/off control]
DHW heating mode timer : Mode timer manage the operation terms when there are simultaneous
FSV #3024 (minimum Space heating operating time, Default 5 min., Range 1 ~ 20 min.),
#3025 (maximum DHW time, Default 30 min., Range 5 ~ 95 min.), #3026(maximum space heating
operation time, Default 3 hour, Range 0.5 ~ 10 hour)
Maximum operation time is applied only when both DHW and Space heating request operation.
DHW or Space heating operates continuously until reaching at target temperature without time
limitation in the single operation.
[Time variation control of DHW and space heating mode]
English
32
T
> T
U
HP MAX
T(C)
T
U
#3021
T
HP MAX
#3022
T
HP OFF
#3023
T
HP ON
requests of space heating/cooling and DHW.
Space heating
1
request
0
DHW request
1
0
DHW operation
1
Space heating
0
operation
#3025
T
< T
Tu : User set temp.
U
HP MAX
T(C)
T(C) : Temp. (Celsius)
#3021
T
HP MAX
T
=T
U
HP OFF
#3023
T
HP ON
#3024
#3026
t