Field Setting Mode; Air To Water Heat Pump: Only Ae*** Model - Samsung MIM-E03EN User Manual

Air to water heat pump, wired remote controller, control kit
Hide thumbs Also See for MIM-E03EN:
Table of Contents

Advertisement

Field setting mode

Air to Water Heat Pump: Only AE*** Model

CAUTION
Set the FSV value of the product other than the specified models by referring to the FSV label provided
with the manual of the product, and then attach it on the control box's cover. The FSV values in the table
are applied to the specified models.
NOTE
Be sure to reset the power when changing the FSV (#3041 to 3046) of disinfection operation and the
FSV (#5011 to 5019) of setting the outing mode.
Field Setting Value (FSV) 10**
Code 10** : Upper and lower temperature limits of each operation mode of wired remote controller
Heating(Water Out, Room), Cooling(Water Out, Room), DHW(Tank)
The values in the following table are just examples for your understanding.
Main Menu
Menu
& Code
Water Out Temperature for
Cooling
Remote
Controller
Water Out Temperature for
Setting
Range Code
Heating
10**
DHW
DHW tank Temperature
NOTE
The FSV #3011 in the wired remote controller should be set to 1 or 2 to use the DHW mode.
The value is determined according to the type of outdoor unit.
1)*
24 English
Function
Item
Max
Cooling
Min
Max
Room Temperature for
Cooling
Min
Max
Heating
Min
Max
Room Temperature for
Heating
Min
Max
Min
MODEL CODE :
AE200(260)RNW***
Sub
Code
Setting Standard
Step Unit
Default Min. Max.
1
1011
25
1
1012
16
1
1021
30
1
1022
1
1031 65/70
1)*
1
1032
25
1
1041
30
1
1042
16
1
1051
55
1
1052
40
MODEL CODE :
MIM-E03CN /
MIM-E03EN
Setting Standard
Default Min.
25
25
5
16
5
30
30
37 65/70
65/70
37
1)*
1)*
15
37
25
15
30
30
16
16
16
50
70
55
50
30
40
40
30
Max.
25
30
65/70
1)*
37
30
70
40