Samsung MIM-E03EN User Manual page 28

Air to water heat pump, wired remote controller, control kit
Hide thumbs Also See for MIM-E03EN:
Table of Contents

Advertisement

Field setting mode
External Room Thermostat (Field Option)
Terminal #1 (#2091, Default 0 for no usage), #2 (#2092, Default 0 for no usage)
To use wired remote controller for heating/cooling operation, both of the above settings should be
set to 0 simultaneously. If not, thermostat controls system.
To use the External Room Thermostat option, set the 2-zone control option (FSV #4061) to "0" for
disabling it.
If set to #2091/#2092 1, the compressor can be turned on or off only by the thermostat.
If set to #2091/#2092 2~4, the compressor can be turned on or off by the thermostat or according
#2092 2,
Water pump
ON
OFF
1
0
Water law
1min
Thermo
#2092 4,
Water pump
ON
OFF
1
0
Water law
3min 7min
Thermo
Types of water law used by room thermostat operation will follow the FSV settings defined in #2041
During the thermostat operation, the user has the possibility to shift up or down the target water
English
28
Time
Time
Time
Time
3min
7min
#2092 3,
Water pump
ON
OFF
1
0
Water law
Thermo
Time
Time