Code: 20**
#2021 or #2031
#2022 or #2032
1) In case of outdoor temperature (Ta)°C < (Code #2011)°C
Code #2041: 1 (Floor) Setting Ts = #2021
Code #2041: Setting 2 (Fan Coil Unit) Ts = #2031
2)
Code #2041: Setting 1(Floor) Ts = #2021 + (#2022 - #2021) / (#2012 - #2011) * (Ta - #2011)
Code #2041: Setting 2(Fan Coil Unit) Ts = #2031 + (#2032 - #2031)/(#2012 - #2011) * (Ta - #2011)
3)
Code #2041: Setting 1(Floor) Ts = #2022
Code #2041: Setting 2(Fan Coil Unit) Ts = #2032
2091 : Application of External thermostat in user's system
0: Disabled
1: Turn on or off the device using the thermostat
2: Turn on or off the device in connection with the thermostat and discharged water temperature
settings
Discharged water temperature setting when a thermostat is connected
Cooling mode: #1012 value (Wired remote controller category field specifications)
Heating mode: Value set according to water laws
Code 30**
User's options for domestic hot water (DHW) tank heating
3011: Application of DHW tank
302*: Heat pump variables for tank temp. control and combination with booster heater
3021: Maximum DHW tank temperature with heat pump (H/P) operation
3022: Offset temperature of forced DHW's thermo off (Only Hydro Unit / Not Hydro Unit HT)
T
S
#2011
T
Target water temperature
S
T
Ambient (outdoor) temperatur
A
#2012
T
A
English