P3: INPUT CURRENT OVERLOAD PROTECTION
DEFINITION
Input current overload protection is activated when current is drawn above the allowable limit.
POSSIBLE CAUSES
• Stop valve is closed
• Improper power supply
• Excess refrigerant in the system
• Damaged valve or filter resulting in large pressure ratio
• Damaged main board
A210287
Fig. 52 —P3 Troubleshooting Chart