Carrier 38VMH-1P Service Manual page 43

Outdoor units for variable refrigerant flow vrf heat pump system
Table of Contents

Advertisement

:
P1: HIGH PRESSURE PROTECTION
DEFINITION
High pressure switch is activated for pressure > 638 psi.
POSSIBLE CAUSES
• Stop valve is closed
• The heat exchanger is dirty or blocked
• Excess refrigerant in the system
• Damaged main board
• Damaged high pressure sensor
• Refrigerant is blocked in high pressure zone
A210285
Fig. 50 —P1 Troubleshooting Chart
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
43

Advertisement

Table of Contents
loading

This manual is also suitable for:

38vmb036hds3-138vmb048hds3-138vmb060hds3-1

Table of Contents