OUTDOOR FAN CONTROL
There are eight step levels (W1 to W8); however, OFF = 0 rpm is not displayed as a step level.
FAN
Up
RPM
Down
Fan Control in Cooling Mode
Table 27 —Fan Control by Outdoor Temperature (T4) and Compressor Frequency
38VMB036~060HDS3-1
T4 ≥ 84.2°F
62.6°F ≤ T4 < 84.2°F
41°F ≤ T4 < 62.6°F
32°F ≤ T4 < 41°F
23°F ≤ T4 < 32°F
T4 < 23°F
SEQUENCE:
1. Outdoor fan will come on (W7) for 20 seconds before compressor starts.
2. Outdoor fan continues to run (W7) for another 20 seconds after compressor starts.
3. Based on outdoor temperature (T4), outdoor fan will follow step level for another 40 seconds as shown in table above.
4. 60 seconds after the compressor starts, outdoor fan step level is determined based on T4, T5, and Tc.
Method B shows the T4 < 23°F operation as mentioned in the above table.
Fig. 33 —Fan Control Correction by Compressor Discharge Temperature (T5)
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Table 26 —Eight Steps of Outdoor Fan Control
OFF
W1
W2
0
300
330
0
0
300
Frequency < 34
Minimum
Maximum
W2
W7
W1
W4
OFF
W2
OFF
W1
OFF
W1
OFF
OFF
Fig. 32 —Fan Control by Condensing Temperature (Tc)
L*: Outdoor fan runs at maximum speed according to fan control by T4 and frequency
table. Under the condition that the maximum speed is OFF, use W1 instead.
W3
W4
400
460
380
440
34 ≤ Frequency < 48
Minimum
Maximum
W4
W7
W2
W6
W1
W4
W1
W2
W1
W2
OFF
OFF
26
W5
W6
W7
520
630
780
500
610
760
Frequency ≥ 50
Minimum
Maximum
W6
W7
W4
W6
W3
W6
W1
W4
W1
W2
OFF
OFF
A210260A210266