Troubleshooting from Outdoor Unit

Error Code
E2
Communication error between indoor units and outdoor unit
E4
Temperature sensor (T3 or T4) error
E5
Power voltage protection
E6
DC fan error
E7
Discharge temperature sensor (T5) error
E9
EEPROM error
E.9.
Mismatched main chip with EEPROM
EA
DC fans stay at zone A for more than five minutes (i.e. the low pressure is too high) in heating mode
Eb
E6 error more than two times in ten minutes
P1
High pressure protection
P2
Low pressure protection
P3
Input current overload protection
P4
Discharge temperature (T5) protection
P5
Condenser temperature (T3) protection
P8
Fan speed exceeds setpoint for five seconds or more
PE
High indoor coil temperature (T2A) protection
PP
Liquid slugging protection; indoor evaporator super heat too low
F1
DC bus voltage is too low (< 200V DC) for five seconds
H0
Communication error between power driver and main control board
H4
L0 or L1 error more than three times in 60 minutes
L0
Error in compressor module
L1
DC bus under-voltage protection
L2
DC bus over-voltage protection
L4
Compressor MCE error
L8
Compressor speed difference is more than 15 rps in one second
L9
Compressor speed difference between setting speed and running speed is more than 15 rps
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
CAUTION
Be sure to turn off power switch before connecting or
disconnecting the connector. Failure to do so could damage
the board.
Table 35 —Error Code of Outdoor Unit