Step 1.
Touch the static-protective package that contains the new adapter to any unpainted surface on the
outside of the server. Then, take the adapter out of the package and place it on a static-protective
surface.
Step 2.
Remove the OCP 3.0 Ethernet adapter filler if there is.
Step 3.
Install the OCP 3.0 Ethernet adapter.
Note: Ensure that the Ethernet adapter is fully seated and the thumbscrew is securely tightened.
Otherwise, the OCP 3.0 Ethernet adapter will not get full connection and may not function.
Figure 208. OCP 3.0 Ethernet adapter installation
a.
Push the OCP 3.0 Ethernet adapter into the slot until it is fully seated.
b.
Tighten the thumbscrew to secure the card.
Step 4.
Attach the OCP label to the rear of the server.
Figure 209. Attaching the OCP label
After you finish
Complete the parts replacement. See "Complete the parts replacement" on page 381.