IEC 61000-4-6
IEC 61000-4-8
IEC 61000-4-29
IEC 61000-4-11
IEC 61000-4-12
IEC 61000-4-16
IEC 61000-4-17
IEC 60255-5
IEEE 1613 (C37.90.x) EMC Immunity Type Tests
Note
RUGGEDCOM products meet Class 1 requirements for copper Ethernet
configurations and Class 2 for fiber Ethernet configurations. Class 1 allows for
temporary communication loss, while Class 2 requires error-free and interrupted
communications.
RUGGEDCOM RS401
Installation Manual, 11/2022, C79000-G8976-1017-12
Test
Description
Induced
(Conducted) RFI
Magnetic Field
Voltage Dips
and Interrupts
Damped
Oscillatory
Mains Frequency
Voltage
Ripple on DC
Power Supply
Dielectric
Strength
H.V. Impulse
Description
ESD
Enclosure Contact
Enclosure Air
6.2 EMC and Environmental Type Tests
DC Power Ports
AC Power Ports
Signal Ports
D.C Power Ports
AC Power Ports
Earth
Ground Ports
Enclosure Ports
DC Power Ports
30% for 0.1 s, 100% for 0.05 s
AC Power Ports
Signal Ports
2.5 kV common, 1 kV
differential mode at 1 MHz
DC Power Ports
2.5 kV common, 1 kV
differential mode at 1 MHz
AC Power Ports
2.5 kV common, 1 kV
differential mode at 1 MHz
Signal Ports
30 V Continuous, 300 V for 1 s
DC Power Ports
30 V Continuous, 300 V for 1 s
DC Power Ports
Signal Ports
2 kVac (Fail-Safe Relay Output)
DC Power Ports
AC Power Ports
Signal Ports
5 kV (Fail-Safe Relay output)
DC Power Ports
AC Power Ports
Certification
Test Levels
±2 kV Line-to-Earth,
±1 kV Line-to-Line
±4 kV Line-to-Earth,
±2 kV Line-to-Line
10 V
10 V
10 V
10 V
40 A/m continuous,
1000 A/m for 1 s
30% for 1 period,
60% for 250 periods
100% for 5 periods,
2
100% for 50 periods
10%
1.5 kVDC
2 kVAC
5 kV
5 kV
Test Levels
±8 kV
±15 kV
Severity
Levels
3
4
3
3
3
3
 
 
 
 
3
3
3
4
4
3
 
 
 
 
 
 
39