Technical specifications
6.1 Technical specifications
Article number
Input delay (for rated value of input voltage)
for standard inputs
–
parameterizable
–
at "0" to "1", min.
–
at "0" to "1", max.
–
at "1" to "0", min.
–
at "1" to "0", max.
Cable length
shielded, max.
•
unshielded, max.
•
Encoder
Connectable encoders
2-wire sensor
•
–
permissible quiescent current (2-wire
sensor), max.
Isochronous mode
Isochronous operation (application synchro-
nized up to terminal)
Interrupts/diagnostics/status information
Diagnostics function
Alarms
Diagnostic alarm
•
Diagnostic messages
Diagnostic information readable
•
Monitoring the supply voltage
•
–
parameterizable
Monitoring of encoder power supply
•
Wire-break
•
Short-circuit
•
Group error
•
Diagnostics indication LED
Monitoring of the supply voltage (PWR-
•
LED)
Channel status display
•
for channel diagnostics
•
for module diagnostics
•
22
6ES7131-6BF01-0AA0
Yes; 0.05 / 0.1 / 0.4 / 0.8 / 1.6 / 3.2 / 12.8 / 20 ms
(in each case + delay of 30 to 500 µs, depending
on line length)
0.05 ms
20 ms
0.05 ms
20 ms
1 000 m
600 m
Yes
2 mA
No
Yes
Yes
Yes
Yes
Yes
No
No
No
Yes
Yes; green PWR LED
Yes; Green LED
No
Yes; green/red DIAG LED
Digital input module DI 8x24VDC BA (6ES7131-6BF01-0AA0)
Manual, 02/2019, A5E34941724-AB