Air Purge On The Central Water Loop Circuit; To Perform An Operation Test Run; To Perform An Actuator Test Run - Daikin EWSAH06D 9W Series Installer's Reference Manual

Table of Contents

Advertisement

12
|
Commissioning

12.4.2 Air purge on the central water loop circuit

12.4.3 To perform an operation test run

12.4.4 To perform an actuator test run

Installer reference guide
212
5 Select OK to confirm.
Result: The air purge starts. It stops automatically when done.
6 To stop the air purge manually:
1 In the menu, go to Stop air purge.
2 Select OK to confirm.
Install the air-purge (field supplied) on top of the unit and at the highest point on
the return pipe of the central water loop circuit inside the apartment or residence.
Follow the instructions that are included with the air purge system.
Conditions: Make sure all operation is disabled. Go to [C]: Operation and turn off
Room, Space heating/cooling and Tank operation.
1 Set the user permission level to Installer. See
the user permission
2 Go to [A.1]: Commissioning > Operation test run.
3 Select a test from the list. Example: Heating.
4 Select OK to confirm.
Result: The test run starts. It stops automatically when ready
(±30 min).
To stop the test run manually:
1 In the menu, go to Stop test run.
2 Select OK to confirm.
INFORMATION
If the outdoor temperature is outside the range of operation, the unit may NOT
operate or may NOT deliver the required capacity.
To monitor leaving water and tank temperatures
During test run, the correct operation of the unit can be checked by monitoring its
leaving water temperature (heating/cooling mode) and tank temperature
(domestic hot water mode).
To monitor the temperatures:
1 In the menu, go to Sensors.
2 Select the temperature information.
Purpose
Perform an actuator test run to confirm the operation of the different actuators.
For example, when you select Pump, a test run of the pump will start.
Conditions: Make sure all operation is disabled. Go to [C]: Operation and turn off
Room, Space heating/cooling and Tank operation.
4
level" [
 134].
"To change
EWSAH/X06D
Daikin Altherma 3 WS
4P675764-1 – 2022.04

Advertisement

Table of Contents
loading

This manual is also suitable for:

Altherma 3 wsEwsax06d 9w seriesEwsax-d9wEwsah-d9w

Table of Contents