Technical Data; Operation - Viking VK4651 Technical Data Manual

Quick response concealed pendent sprinklers
Table of Contents

Advertisement

Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com
5.

OPERATION

During fire conditions, when the temperature around the sprinkler approaches its operating temperature, the cover plate detaches,
releasing the deflector. Continued heating of the exposed sprinkler causes the heat-sensitive liquid in the glass bulb to expand,
causing the glass to shatter, releasing the pip cap and sealing spring assembly. Water flowing through the sprinkler orifice strikes
the deflector, forming a uniform spray pattern over a specific area of coverage determined by the water supply pressure at the
sprinkler to extinguish or control the fire.
6.
INSPECTIONS, TESTS AND MAINTENANCE
Refer to NFPA 25 for Inspection, Testing and Maintenance requirements.
7.
AVAILABILITY
Viking Sprinklers are available through a network of domestic and international distributors. See The Viking Corporation web site
for the closest distributor or contact The Viking Corporation.
8.
GUARANTEE
For details of warranty, refer to Viking's current list price schedule or contact Viking directly.
Instructions:
(1) Select a Sprinkler Base Part Number
(2) Add the suffix for the desired Finish
(3) Add the suffix for the desired Sprinkler Temperature Rating
(4) Order a cover plate (refer to Table 2)
Example:
23233AE = 200 °F (93 °C) Temperature Rated Sprinkler with a standard Brass finish.
Size
Sprinkler
Base Part
NPT
BSPT
No.
Inch
mm
23233
1/2
--
23235
--
15
Accessories
Sprinkler Wrenches and Tools (see Figure 1):
A. Installation wrench: 24339
B. Protective cap removal tool: 24340
C. Concealed Cover Plate Installer Tool Part Number: 14412
D. Large Concealed Cover Plate Installer Tool Part No. 14867
Sprinkler Cabinet:
Part number 01731A.
Footnotes
Where a dash (-) is shown in the Finish suffix designation, insert the desired Temperature Rating suffix. See example above.
1.
Based on NFPA 13, NFPA 13R, and NFPA 13D. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having
2.
Jurisdiction. Refer to specific installation standards.
UL Listed as corrosion resistant.
3.
The corrosion resistant coatings have passed the standard corrosion test required by the approving agencies indicated in the Approval Chart. These tests cannot and
4.
do not represent all possible corrosive environments. Prior to installation, verify through the end-user that the coatings are compatible with or suitable for the proposed
environment. For automatic sprinklers, the ENT coating is applied to all exposed exterior surfaces, including the waterway.
Requires a 3/8" ratchet (not available from Viking).
5.
The installer tool is for push-on style cover plates only.
6.
Requires a peice of 1" PVC pipe or similar to attach.
7.
Form No. F_040320
21.12.02 Rev 21.3

TECHNICAL DATA

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
TABLE 1: ORDERING INFORMATION
1: Finishes
Description
Suffix
1
Brass
A
ENT
JN
3,4
5
2: Temperature Ratings
Sprinkler
Nominal
Temperature
Rating
Classification
Oridinary
155 °F (68 °C)
Intermediate
175 °F (79 °C)
Intermediate
200 °F (93 °C)
(available since 2007)
6
(available since 2007)
6
QUICK RESPONSE
CONCEALED PENDENT
SPRINKLERS
VK4651 (K4.2)
Bulb
Max. Ambient
Color
Ceiling Temperature
Red
100 °F (38 °C)
Yellow
150 °F (65 °C)
Green
150 °F (65 °C)
Page 2 of 8