Shut Down Power; Remove The Dynaview™ Display; Prepare Unit For Installation - Trane Tracer AdaptiView Installation Instructions Manual

Rtac rotary chiller display upgrade kit
Hide thumbs Also See for Tracer AdaptiView:
Table of Contents

Advertisement

Installation

Shut Down Power

WARNING
Hazardous Voltage w/Capacitors!
Failure to disconnect power and discharge capacitors
before servicing could result in death or serious injury.
Disconnect all electric power, including remote
disconnects and discharge all motor start/run
capacitors before servicing. Follow proper lockout/
tagout procedures to ensure the power cannot be
inadvertently energized. For variable frequency drives or
other energy storing components provided by Trane or
others, refer to the appropriate manufacturer's literature
for allowable waiting periods for discharge of
capacitors. Verify with an appropriate voltmeter that all
capacitors have discharged.
For additional information regarding the safe discharge
of capacitors, see PROD-SVB06*-EN
1. Using lockout/tagout safety procedures, shut down the
chiller's main power.
2. Open all starter and control panel disconnect switches
and secure them in the open position.
3. Confirm that the power is off to the control panel of the
chiller.
Remove the DynaView™ Display
1. Remove the louver, side, and control enclosure panels.
See
Figure
3.
2. Remove the 4 fasteners holding the DynaView display
to the Unit.
3. Unplug the 4-wire Phoenix connector from the
DynaView display and remove the DynaView display
from the unit.
Figure 3.
Louver panel removal
12

Prepare Unit for Installation

WARNING
Risk of Electrocution!
Failure to follow instructions could result in death or
serious injury. Before and during drilling operations
ensure that all electrical cables and wires are not in the
path of the drill bit.
1. Cover unit control cover back plate with plastic to
prevent metal chips intrusion.
NOTICE:
Equipment Damage!
Failure to prevent metal chips from lodging against or
inside of the electrical components can cause them to
fail when they are energized.
2. Using the template provided, mark the location of the
four mounting holes required for the UC800 back plate
assembly. The template should be positioned so the
lower holes are approximately 6.5" from the bottom of
the cabinet. See
Figure 4, p.
Note: Actual size back plate template is found in
Figure 56, p.
51.
3. Use a 17/64" drill bit to drill the four holes. See
Figure
4.
Figure 4.
UC800 back plate assembly mounting hole
(a)
locations
2.75"
MINIMUM
5.0"
8.0"
4X
17/64"
(BACK PLATE)
2.3"
(a) Actual size back plate template is found in
12.
CONTROL PANEL
FRONT
7/8" (USB PORT)
26.0"
6.5"
Figure 56, p. 51
.
RCDA-SVN002C-EN

Advertisement

Table of Contents
loading

Table of Contents