Honeywell DACT-E3 Product Installation Document page 7

Digital alarm communicator transmitter
Table of Contents

Advertisement

Section 3: Wiring Connections (Continued)
Figure 3.1 illustrates the wiring connections for the DACT-E3 sub-assembly.
FROM ILI-MB-E3 OR ILI95-MB-E3 TB3-1 OR FROM SLP-E3 TB3-1
FROM ILI-MB-E3 OR ILI95-MB-E3 TB3-2 OR FROM SLP-E3 TB3-2
FROM ILI-MB-E3 OR ILI95-MB-E3 TB3-6 OR FROM SLP-E3 TB2-3
FROM ILI-MB-E3 OR ILI95-MB-E3 TB3-7 OR FROM SLP-E3 TB2-4
LINE 1 RING OUT TO PREMISES PHONE(S)
LINE 2 RING OUT TO PREMISES PHONE(S)
DACT-E3 Product Installation Document — P/N 9000-0581:J6 12/16/2019
RS485 COM A OUT TO NEXT DEVICE
RS485 COM B OUT TO NEXT DEVICE
TELCO LINE 1 TIP IN FROM STREET
TELCO LINE 1 RING IN FROM STREET
LINE 1 TIP OUT TO PREMISES PHONE(S)
TELCO LINE 2 TIP IN FROM STREET
TELCO LINE 2 RING IN FROM STREET
LINE 2 TIP OUT TO PREMISES PHONE(S)
IMPORTANT
DACT-E3 MUST BE THE FIRST
DEVICE TO THE TELCO LINES
Figure 3.1 DACT-E3 Installation Wiring Diagram
LED1 LINE 1 STATUS:
OFF
= LINE 1 INACTIVE
ON
= LINE 1 TRANSMITTING DATA
FLASHING = LINE 1 FAULT
LED2 LINE 2 STATUS:
OFF
= LINE 2 INACTIVE
ON
= LINE 2 TRANSMITTING DATA
FLASHING = LINE 2 FAULT
LED3 STANDBY:
OFF
= NORMAL STANDBY MODE
ON
= TRANSMITTING OR IN TROUBLE
1
RS485 COM A IN
1
RS485 COM B IN
2
RS485 COM A OUT
3
4
RS485 COM B OUT
5
24 VDC (+)
6
SYS NET (-)
6
TB1
LED3
STANDBY LINE2
STATUS
1
1
2
3
4
5
K1
6
1
7
8
8
TB2
LED2
LED1
LINE1
STATUS
T1
7

Advertisement

Table of Contents
loading

Table of Contents