Honeywell DACT-E3 Product Installation Document page 10

Digital alarm communicator transmitter
Table of Contents

Advertisement

For Contact ID and SIA Formats:
GG
= In standalone systems, the group number assigned to the device, 00-99.
= In networked systems, the node number where the device is located, 00-64 (000-122 in multi-ring networks).
0G
= In only multi-ring systems, represents the 100s digit of the node address.
For Contact ID and SIA Formats: (Continued)
T = Type of device or event causing the event to be reported.
0 = Any Device not listed below
1 = General Alarm Device
2 = Manual Station Alarm
3 = Supervisory Device (Non-latching)
4 = Supervisory Device (Latching)
5 = Waterflow (Non-silenceable)
6 = Smoke Alarm
7 = Non-reporting Device
8 = Multi-level Device
9 = CO/Gas Alarm Device
Note: Special AMM/PIDs include the following functions: Reset Switch, Silence Switch, Drill Switch, Alarm Acknowledge Switch,
Trouble Acknowledge Switch.
Table 4.2.1.1 DACT-E3 Contact ID Event Reporting Codes for Standard Formats
4.2.2 Custom Formats
The DACT-E3 can be configured to allow each SLC device to report a unique 3-digit code by selecting the Custom DACT
Reporting Feature. The user must specifically enable this feature through configuration programming by using
CAMWorks™. If you enable the Custom DACT Reporting feature, the system uses the Custom codes or optional fields. The
system substitutes the custom formats or optional fields in place of the standard codes. To enable this feature, each ILI-MB-
E3, ILI-S-E3 or SLP-E3 must have V1.3-806 or higher ILI Firmware installed. This feature is also available for the ILI95-
MB-E3, ILI95-S-E3 or SLP-E3. For information on the DACT-E3 Contact ID Event Reporting Codes for Custom Formats,
refer to Table 4.2.2.1. Figure 4.2.2.1 illustrates an example of the DACT Contact ID Reporting Codes for Custom formats
used to configure the following types of systems.
S T A N D A L O N E S Y S T E M S
C O N T A C T ID F O R M A T
N O T E : G r o u p N u m b e r s a r e
t r u n c a t e d t o r a n g e [ 0 0 - 9 9 ] .
N E T W O R K E D S Y S T E M S
C O N T A C T ID F O R M A T
N E T W O R K S Y S T E M S
C O N T A C T ID F O R M A T
N O T E : N o d e N u m b e r s a b o v e 9 9
a r e t r u n c a t e d t o r a n g e [ 0 0 - 9 9 ] .
Figure 4.2.2.1 Example of the DACT-E3 Contact ID Event Reporting Codes for Custom Formats
..
NOTE: To use the Custom DACT Reporting Feature, all ILI-MB-E3, ILI-S-E3 and SLP-E3 nodes on the network
must have V1.3-806 ILI Firmware installed as the minimum requirement. For additional information, refer to the
CAMWorks Online Help.
10
[1 ]= N e w E v e n t
[3 ]= R e s to r a l
E X A M P L E
N e w E v e n t
S IN G L E - R IN G
[1 ]= N e w E v e n t
[3 ]= R e s to r a l
E X A M P L E
N e w E v e n t
M U L T I- R IN G
[1 ]= N e w E v e n t
[3 ]= R e s to r a l
E X A M P L E
N e w E v e n t
DACT-E3 Product Installation Document — P/N 9000-0581:J6 12/16/2019
C O N T A C T ID F O R M A T
[ R ]
[ E E E ]
[ G G ]
E v e n t T y p e
G r o u p
N u m b e r
1
1 1 0
0 0
F ir e A la r m
G r o u p 0 0
C O N T A C T ID F O R M A T
[ R ]
[ E E E ]
[ N N ]
E v e n t T y p e
N o d e
N u m b e r
1
1 1 0
0 9
F ir e A la r m
N o d e 0 9
C O N T A C T ID F O R M A T
[ R ]
[ E E E ]
[ N N ]
E v e n t T y p e
N o d e
N u m b e r
1
1 1 0
0 9
N o d e 0 9
F ir e A la r m
o r 1 0 9
[ U U U ]
C u s to m D e v ic e ID
0 9 5
C u s to m ID 0 9 5
[ U U U ]
C u s to m D e v ic e ID
5 0 0
C u s to m ID 5 0 0
[ U U U ]
C u s to m D e v ic e ID
8 8 0
C u s to m ID 8 8 0

Advertisement

Table of Contents
loading

Table of Contents