2.3.1.2 DACT-E3 Installation in an S3 Series, Cabinet Configuration
In an S3 Series, SLP-BB cabinet configuration, the PCB orientation of the DACT-E3 sub-assembly is usually installed above the
SLP-E3 sub-assembly as part of a backbox configuration. To install the DACT-E3, refer to the following instructions.
1.
Insert and secure four standoffs (3/16" HEX #4-40, x 1 1/) to the SLP-E3 as shown in Location 1 of Figure 2.3.1.2.1.
2.
Align and place the DACT-E3 on top of the SLP-E3.
3.
To mount the DACT-E3 to the SLP-E3, insert and secure four screws (#4-40 x 1/4") into the four standoffs as shown in
Location 2 of Figure 2.3.1.2.1.
(# 4 -4 0 x 1 -½ " (3 8 .1 0 m m ))L G
Figure 2.3.1.2.2 illustrates the DACT-E3 installed in the SLP-BB cabinet.
NON POWER-LIMITED)
DACT-E3 Product Installation Document — P/N 9000-0581:J6 12/16/2019
S T A N D O F F , M /F ,
(4 P L A C E S )
S C R E W ,
(# 4 -4 0 x ¼ " (6 .3 5 m m ))
L G , P H P D S E M S
(4 P L A C E S ) D A C T T O
S T A N D O F F M O U N T IN G
Figure 2.3.1.2.1 DACT-E3 to S3 Mounting Plate Installation
AUXILIARY RS485
FROM DACT-E3 TB2
(CLASS 2
POWER-LIMITED)
TELEPHONE LINES
FROM DACT-E3 TB2
(CLASS 2
Figure 2.3.1.2.2 DACT-E3 Installed in the SLP-BB Cabinet