Control Module - Abnormal Led Diagnostics - Leviton i Series e User Manual

Leviton i series i series e dimmer racks: user guide
Table of Contents

Advertisement

1.8
Control Module – Abnormal LED Diagnostics
There are several other Led conditions which the control module LED's will indicate which are not directly
indicated by their nomenclature. They are as follows:
LED's won't light at all :
The 3 Phase LED's chase.
LED's blink briefly, then nothing.
[Repeats]
LED's blink briefly, then RED
Phase A LED comes on. [Repeats]
LED's blink briefly, then RED
Phase A LED comes on. Analog Led
Blinks at least once. [Repeats]
LED's blink briefly, then RED
Phase A LED comes on. Analog Led
blinks. Phase B LED comes on.
Analog LED blinks at least once.
[Repeats]
After All three processors boot,
One or more of the power led's flash.
After All three processors boot,
One or more of the power led's
turn off.
After All 3 processors boot, the
Diagnostics led stays lit, along
with the 3 Power LED's, but the
control module runs a circular chase
pattern between DMX OK,ANALOG,
PANIC, AND BACKUP for about
30 seconds then operates normally.
i Series e Users Guide
LIT-31903-00
No power to rack, or no power to control module.
Pull the control module. This will turn on the fan to full if there
is power to the rack. Check the 3 phase power harness that
connects the control module drawer to the side of the rack.
The Line frequency is out of specification. Displayed on HHR.
Line power frequency has to be between 47-63hz.
Main Processor (U5)not getting through RAM check.
Main Processor (U5)not booting properly.
Main Processor booting properly
B Processor (U19) not booting properly.
Main Processor booting properly
B Processor booting properly
C Processor (U28) not booting properly
Feeder Line voltage is too high.
[above 135VAC for a 120VAC system]
[above 260VAC for a 240VAC system]
Feeder Line voltage is too low or off.
[below 90VAC for a 120VAC system]
[below 190VAC for a 240VAC system]
The main processor can't get the configuration from the
backplane. It will try to read the backplane for about 30
seconds, then it will give up and will process normally
the default thumbwheel DMX-512 patch settings [1-15].
Custom patches and snapshot scenes will not be available.
Page 11 of 35

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

I96quadI48quadI24e w/jp1 inI24e w/jp1 outI 48eI 96e

Table of Contents