Briggs & Stratton 040661 Installation And Operation Manual page 25

Single phase air-cooled standby generator system 17 kw/20 kw/26 kw
Table of Contents

Advertisement

Installation
PIN
DESCRIPTION
NUMBER
1
+12V
2
GND
3
Xfer
4
2-WIRE START #18 AWG (1 mm2) conductors,
5
2-WIRE START #18 AWG (1 mm2) conductors,
6
E-STOP
7
E-STOP
9
VIN+
(+12V)
10
(D+)
11
(D-)
12
GND
13
+12V
14
(A)
15
(B)
16
GND
25
Utility
26
Utility
• For power output connection (L1, L2, Neutral (N), and
Ground), refer to the National Electric Code (NEC)
and local codes.
• For communication wires use 300V wire and #18 AWG
(1 mm2) twisted-pair conductors that do not exceed a
length of 500 ft (150 m).
Part No. 80106286
Revision C
WIRE TYPE
#18 AWG (1 mm2) conductors,
600V minimum, 90° C Cu wire.
#18 AWG (1 mm2) conductors,
600V minimum, 90° C Cu wire.
#18 AWG (1 mm2) conductors,
600V minimum, 90° C Cu wire.
600V minimum, 90° C Cu wire.
600V minimum, 90° C Cu wire.
#18 AWG (1 mm2) conductors,
600V minimum, 90° C Cu wire.
#18 AWG (1 mm2) conductors,
600V minimum, 90° C Cu wire.
#18 AWG (1 mm2) conductors,
600V minimum, 90° C Cu wire.
#18 AWG (1 mm2) conductors,
600V minimum, 90° C Cu wire.
#18 AWG (1 mm2) conductors,
600V minimum, 90° C Cu wire.
#18 AWG (1 mm2) conductors,
600V minimum, 90° C Cu wire.
#18 AWG (1 mm2) conductors,
600V minimum, 90° C Cu wire.
#18 AWG (1 mm2) conductors,
600V minimum, 90° C Cu wire.
#18 AWG (1 mm2) conductors,
600V minimum, 90° C Cu wire.
#18 AWG (1 mm2) conductors,
600V minimum, 90° C Cu wire.
#14 AWG [2.50 mm2] 600V
minimum, 90° C Cu Wire.
#14 AWG [2.50 mm2] 600V
minimum, 90° C Cu Wire.
CONNECT TO
Transfer Switch
Basic Controller J7-8
12VDC
Transfer Switch Basic
Controller J7-7 GND
Transfer Switch Basic
Controller J7-4 T/R
Refer to Transfer
Switch Manual to
verify if this function
is available.
E-Stop Switch
E-Stop Switch
Refer to the Amplify
Gateway Manual.
Refer to the InfoHub™
Premium Manual.
Transfer Switch
Utility
Transfer Switch
Utility
• When connecting to the terminal block, fasten only
one wire to each connector screw.
• Torque terminal block screws to 4.4 in-lb (0.5 N·m).
• Torque circuit breaker connections to 45 in-lb (5 N·m).
25
Electrical Field Connections
NOTES
Transfer Switch Transfer Signal
(only works with Basic Transfer
Switch Controller)
Contact Close for
GENSET Start. (Only for
Transfer Switch that provides
this option).
Mains monitoring must be
disabled in the controller.
Contact Open to Shutdown
GENSET
Comm to WIFI Module
Twisted Pair #1: +12V and GND
Twisted Pair #2: (D+) and (D-)
Comm to Cellular Module
Twisted Pair #1: +12V and GND
Twisted Pair #2: (A) and (B)
Voltage Sensing for GENSET
Start. Use either this signal
or two-wire Start Signal for
GENSET Start Signal (still
required in two-wire start
configuration for battery
charger).