PROFINET IO
6.4 Interrupt, error and system messages
Combination of "ChannelProperties.Qualifier (Bit 9 / 10)" and
"ChannelProperties.Specifier (Bit 11 / 12)"
Mainte-
nance Re-
quired Bit 9
0
1
70
Mainte-
Specifi-
Meaning
nance De-
er bit
manded
12 / 11
Bit 10
0
00
All lower-level diagnoses are
no longer pending.
01
Diagnosis is pending.
10
Diagnosis is no longer pend-
ing.
11
Status message. Only possible
for manufacturer-specific
errors.
1
00
Reserved
01
Maintenance required is pend-
ing.
10
Maintenance required is no
longer pending.
11
Maintenance required is no
longer pending; all others are
still pending.
0
00
Reserved
01
Maintenance demanded is
pending.
10
Maintenance demanded is no
longer pending.
11
Maintenance demanded is no
longer pending; all others are
still pending.
1
00
Reserved
01
Stepped diagnosis is pending.
10
Stepped diagnosis is no longer
pending.
11
Stepped diagnosis is no longer
pending; all others are still
pending.
Diagnosis in the
SIMATIC S7 300 and
SIMATIC S7 400 user pro-
gram
Evaluation of diagnostic
alarms with SFB54 in OB82
Evaluation of diagnostic
alarms with SFB54 in OB82,
data set reading with SFB52
Evaluation of diagnostic
alarms with SFB54 in OB82
–
Evaluation of diagnostic
alarms with SFB54 in OB82,
data set reading with SFB52
Evaluation of diagnostic
alarms with SFB54 in OB82
–
Evaluation of diagnostic
alarms with SFB54 in OB82,
data set reading with SFB52
Evaluation of diagnostic
alarms with SFB54 in OB82
–
Evaluation of diagnostic
alarms with SFB54 in OB82,
data set reading with SFB52
Evaluation of diagnostic
alarms with SFB54 in OB82
3WA Air Circuit Breaker Communication
System Manual, 11/2021, 92310000004-02