PROFINET IO
6.3 Metering values, addressing und data traffic
Module name
Status of IO outputs
Selection of the modules
The 3WA circuit breaker has a modular design and can be configured individually in the
project.
• The "3WA status and control" module has the fixed position of slot 1, subslot 1 in the
circuit breaker and is plugged in automatically.
• The "3WA status and control" module contains two input bytes for the binary status
information and two output bytes for control of the circuit breaker.
• If control of the circuit breaker is not required in the system, the "3WA status and control"
module can be replaced with the "3WA status" module. Please note that slot 1 must
always be occupied.
Both the control and the control bytes are implemented according to the LVSG profile of
the PNO (PROFINET user organization).
54
Module 1
Module 2
Module 3
Module 4
Module 5
Length
(bytes)
1
1
1
1
1
3WA Air Circuit Breaker Communication
System Manual, 11/2021, 92310000004-02
In/Out
In
In
In
In
In