Binary status information
The table below contains a description of the binary status information in the cyclic frame:
Byte
n
n + 1
3WA Air Circuit Breaker Communication
System Manual, 11/2021, 92310000004-02
Bit
Value
3WA circuit breaker
0 / 1
0 ... 3
Position of the circuit breaker in the guide frame
0
Disconnected position
1
Connected position
2
Test position
3
Circuit breaker not available
2 / 3
0 ... 3
Status of the circuit breaker
0
Not used
1
Open
2
Closed
3
Circuit breaker has tripped and is open
4
Ready-to-close
5
Undervoltage release charged
6
Stored-energy spring is charged
7
Overload warning is pending (overload protection is active)
0
An activated threshold has been exceeded
1
A warning message is pending
2
Write protection not active, remote changes allowed
3
4 / 5 / 6
0 ... 7
Reason for last trip
0
No trip or last trip acknowledged
1
Overload protection, long-time delayed (L tripping)
2
Instantaneous short-circuit protection (I tripping)
3
Short-time delayed short-circuit protection (S tripping)
4
Ground-fault protection (G tripping)
5
Extended protective function trip
6
7
7
6.3 Metering values, addressing und data traffic
PROFINET IO
55