Energy data profile e3 Energy Enhanced
Energy data profile e3 is for integration of the 3WA circuit breaker in the Energy Suite profile.
The predefined data blocks cannot be modified.
Byte
0..3
4..7
8..11
11..15
16..19
20..24
24..31
32..39
40..47
48..55
56..59
60..63
64..67
68..71
72..75
76..79
80..83
84..87
88..91
92..95
96..99
100..103
3WA Air Circuit Breaker Communication
System Manual, 11/2021, 92310000004-02
Definition
Default
Data block 1
Active power L1 (float)
Data block 2
Active power L2 (float)
Data block 3
Active power L3 (float)
Data block 4
Reactive power L1 (float)
Data block 5
Reactive power L2 (float)
Data block 6
Reactive power L3 (float)
Data block 7
Total active energy import (double)
Data block 8
Total active energy export (double)
Data block 9
Total reactive energy import (double)
Data block 10
Total reactive energy export (double)
Data block 11
Voltage UL1-N (float)
Data block 12
Voltage UL2-N (float)
Data block 13
Voltage UL3-N (float)
Data block 14
Voltage UL1-UL2 (float)
Data block 15
Voltage UL2-UL3 (float)
Data block 16
Voltage UL3-UL1 (float)
Data block 17
Current L1 (float)
Data block 18
Current L2 (float)
Data block 19
Current L3 (float)
Data block 20
Power factor L1 (float)
Data block 21
Power factor L2 (float)
Data block 22
Power factor L3 (float)