8.3 Precautions when charging refrigerant

8.4 To determine the additional refrigerant amount

8.5 To determine the complete recharge amount

8.6 To charge additional refrigerant

RXF50~71D5V1B
R32 split series
4P519439-15Q – 2021.10
INFORMATION
Also read the precautions and requirements in the following chapters:
"2 General safety
"7.1 Preparing refrigerant
If the total liquid piping
length is...
≤10 m
>10 m
If the total liquid piping
length is...
≤10 m
>10 m
INFORMATION
Piping length is the one-way length of liquid piping.
INFORMATION
If a complete recharge is necessary, the total refrigerant charge is: the factory
refrigerant charge (see unit name plate) + the determined additional amount.
WARNING
Only use R32 as refrigerant. Other substances may cause explosions and
accidents.
R32 contains fluorinated greenhouse gases. Its global warming potential (GWP)
value is 675. Do NOT vent these gases into the atmosphere.
When charging refrigerant, ALWAYS use protective gloves and safety glasses.
precautions" [
4
 5]
4
piping" [
 35]
For ARXM71R
Do NOT add additional refrigerant.
R=(total length (m) of liquid piping⁠ – ⁠ 1 0 m)×0.035
R=Additional charge (kg) (rounded in units of
0.01 kg)
For other outdoor units
Do NOT add additional refrigerant.
R=(total length (m) of liquid piping⁠ – ⁠ 1 0 m)×0.020
R=Additional charge (kg) (rounded in units of
0.01 kg)
8
Charging refrigerant
|
Then...
Then...
Installer reference guide
47