8.3 Precautions when charging refrigerant
8.4 To determine the additional refrigerant amount
8.5 To determine the complete recharge amount
8.6 To charge additional refrigerant
RXF50~71D5V1B
R32 split series
4P519439-15Q – 2021.10
INFORMATION
Also read the precautions and requirements in the following chapters:
▪
"2 General safety
▪
"7.1 Preparing refrigerant
If the total liquid piping
length is...
≤10 m
>10 m
If the total liquid piping
length is...
≤10 m
>10 m
INFORMATION
Piping length is the one-way length of liquid piping.
INFORMATION
If a complete recharge is necessary, the total refrigerant charge is: the factory
refrigerant charge (see unit name plate) + the determined additional amount.
WARNING
▪
Only use R32 as refrigerant. Other substances may cause explosions and
accidents.
▪
R32 contains fluorinated greenhouse gases. Its global warming potential (GWP)
value is 675. Do NOT vent these gases into the atmosphere.
▪
When charging refrigerant, ALWAYS use protective gloves and safety glasses.
precautions" [
4
5]
4
piping" [
35]
For ARXM71R
Do NOT add additional refrigerant.
R=(total length (m) of liquid piping – 1 0 m)×0.035
R=Additional charge (kg) (rounded in units of
0.01 kg)
For other outdoor units
Do NOT add additional refrigerant.
R=(total length (m) of liquid piping – 1 0 m)×0.020
R=Additional charge (kg) (rounded in units of
0.01 kg)
8
Charging refrigerant
|
Then...
Then...
Installer reference guide
47