16 Charging refrigerant

Ambient
Humidity
temperature
≤30°C
75% to 80% RH
>30°C
≥80% RH
Between outdoor and indoor unit
1 Insulate and fix the refrigerant piping and cables as follows:
d
c
a
e
b
f
g
a
Gas pipe
b
Gas pipe insulation
c
Interconnection cable
d
Field wiring (if applicable)
e
Liquid pipe
f
Liquid pipe insulation
g
Finishing tape
2 Install the service cover.
Inside the outdoor unit
To insulate the refrigerant piping, proceed as follows:
b
a
a
Insulation material
b
Caulking etc.
1 Insulate the liquid and gas piping.
2 Wind heat insulation around the curves, and then cover it with
vinyl tape.
3 Make sure the field piping does not touch any compressor
components.
4 Seal the insulation ends (sealant etc.) (b, see above).
5 Where necessary, wrap the field piping with vinyl tape to protect
the insulation against sharp edges.
6 If the outdoor unit is installed above the indoor unit, cover the
stop valves with sealing material to prevent condensed water
on the stop valves from moving to the indoor unit.
NOTICE
Any exposed piping can cause condensation.
7 Reattach the service cover and the piping intake plate.
8 Seal all gaps to prevent snow and small animals from entering
the system.
a
a
Seal
WARNING
Provide adequate measures to prevent that the unit can be
used as a shelter by small animals. Small animals that
make contact with electrical parts can cause malfunctions,
smoke or fire.
Installation and operation manual
34
Minimum thickness
15 mm
20 mm
15.3.5
After charging refrigerant in the system an additional leak test must
be performed. Refer to
leaks after charging
16
16.1
NOTICE
Do not block the air vents. This could affect air circulation
inside the unit.
To check for leaks after charging
refrigerant
"16.6  To check refrigerant piping joints for
refrigerant" [ 4  37].
Charging refrigerant
Precautions when charging
refrigerant
WARNING
▪ Only use R32 as refrigerant. Other substances may
cause explosions and accidents.
▪ R32 contains fluorinated greenhouse gases. Its global
warming potential (GWP) value is 675. Do NOT vent
these gases into the atmosphere.
▪ When charging refrigerant, ALWAYS use protective
gloves and safety glasses.
NOTICE
If the power of some units is turned off, the charging
procedure cannot be finished properly.
NOTICE
Turn ON the power 6 hours before operation in order to
have power running to the crankcase heater and to protect
the compressor.
NOTICE
If operation is performed within 12 minutes after the indoor
and outdoor units are powered on, the compressor will not
operate before the communication is established in a
correct way between outdoor unit(s) and indoor units.
NOTICE
Before
starting
charging
procedures,
7‑segment display indication of the outdoor unit A1P PCB
is as normal (see
"18.1.3  To access mode 1 or
If a malfunction code is present, see
codes" [ 4  47].
problems based on error
NOTICE
Make sure all connected indoor units are recognised (see
setting
[1‑10]
in
"18.1.6 
settings" [ 4  41]).
NOTICE
In case of maintenance and the system (outdoor unit+field
piping+indoor units) does not contain any refrigerant any
more (e.g., after refrigerant reclaim operation), the unit has
to be charged with its original amount of refrigerant (refer
to the nameplate on the unit) and the determined additional
refrigerant amount.
check
if
the
2"  [ 4   41]).
"22.1  Solving
Mode
1:
monitoring
RXYSA8~12AMY1B
VRV 5-S system air conditioner
4P752781-1B – 2024.02