Note
Transmitters set to HART multidrop mode send all saturation and alarm information
digitally; saturation and alarm conditions will not affect the analog output.
Configure alarm and saturation levels using Field
Communicator
From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys
Configure alarm and saturation levels using AMS Device
Manager
Procedure
1. Right click on the device and select Configure.
2. In the left navigation pane select Manual Setup.
3. On the Analog Output Tab find the Alarm and Saturation Levels group box.
4. Enter the High Alarm, High Saturation, Low Saturation and Low Alarm levels to the
5. Select Apply when complete.
Configure alarm and saturation levels using LOI
Reference the
on the LOI.
Figure 2-17: Configuring Alarm and Saturation Values with LOI
VIEW CONFIG
SENSOR CONFIG
UNITS
RERANGE
LOOP TEST
DISPLAY
EXTENDED MENU
EXIT MENU
* Available only if option code (S) or (D) is ordered.
** Available only if option codes (S) and (DC) are both ordered, or if option codes (D) and
(DC) are both ordered.
Emerson.com/Rosemount
desired vales.
Figure 2-17
below to find the alarm and saturation value configuration path
CALIBRAT
DAMPING
VARIABLE MAP
TAG
ALM SAT VALUES
PASSWORD
SIMULATE
HART REV
HOT BACK CONFIG**
DRIFT ALERT**
....
2, 2, 5, 6
ROSEMNT VALUES
NAMUR VALUES
OTHER VALUES
BACK TO MENU
EXIT MENU
Configuration
March 2021
37