Mapping the HART variables
Mapping HART variables using the Field Communicator
The "Variable Mapping" menu displays the sequence of the process variables. Select the
sequence below to change this configuration. The transmitter single sensor input
configuration screens allow selection of the primary variable (PV) and the secondary
variable (SV). When the Select PV screen appears, Snsr 1 must be selected.
The transmitter dual-sensor option configuration screens allow selection of the Primary
Variable (PV), Secondary Variable (SV), Tertiary Variable (TV), and Quaternary Variable
(QV). Variable choices are Sensor 1, Sensor 2, Differential Temperature, Average
Temperature, Terminal Temperature, and Not Used. The 4–20 mA analog signal
represents the Primary Variable.
From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys
Mapping HART variables using the AMS Device Manager
Procedure
1. Right click on the device and select the Configure menu.
2. In the left navigation pane, select Manual Setup then on the HART tab.
3. Map each variable individually or use the Re-map Variables method to guide you
4. Select Apply when complete.
Mapping HART variables using LOI
Follow flow chart to select the desired mapped variables.
Procedure
1. Use the SCROLL and ENTER buttons to select each variable.
2. Save by selecting SAVE as indicated on the LCD screen when prompted.
Emerson.com/Rosemount
through the re-mapping process.
See
Figure 2-5
for an example of a mapped variable with the LOI.
Figure 2-5: Mapping Variables with LOI
VIEW CONFIG
SENSOR CONFIG
UNITS
RERANGE
LOOP TEST
DISPLAY
EXTENDED MENU
EXIT MENU
2, 2, 8, 6
CALIBRAT
DAMPING
VARIABLE MAP
TAG
ALM SAT VALUES
PASSWORD
....
Configuration
March 2021
RE-MAP PV
RE-MAP 2V
RE-MAP 3V
RE-MAP 4V
....
21