Emerson Rosemount 644 Reference Manual page 19

Temperature transmitter
Hide thumbs Also See for Rosemount 644:
Table of Contents

Advertisement

Reference Manual
00809-0200-4728
2.5.2
Verify configuration using the AMS Device Manager
Procedure
1. Right click on the device and select Configuration Properties from the menu.
2. Navigate the tabs to review the transmitter configuration data.
2.5.3
Verify configuration using the LOI
Procedure
1. Press any configuration button to activate the LOI.
2. Select VIEW CONFIG to review the below parameters.
3. Use the configuration buttons to navigate through the menu.
2.5.4
Checking transmitter output
Before performing other transmitter on-line operations, review the transmitter digital
output parameters to ensure that the transmitter is operating properly and is configured
to the appropriate process variables.
Checking or setting process variables
The "Process Variables" menu displays process variables, including sensor temperature,
percent of range, analog output, and terminal temperature. These process variables are
continuously updated. The default primary variable is Sensor 1. The secondary variable is
the transmitter terminal temperature by default.
Check or set process variables using the Field Communicator
From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys
Emerson.com/Rosemount
The parameters to be reviewed prior to installation include:
Tag
Sensor configuration
Units
Alarm and saturation levels
Primary variable
Range values
Damping
3, 2, 1
Configuration
March 2021
19