6 DCP Interface
Bit 7 of byte 1 in master and slave message can initiate a resending of the previous message. In both cases, it is
necessary to respond as follows: The type of message must be maintained (i.e. bytes 4 and 5 are the same as in the
previous message). The actual values are transferred as commands.

Drive Controller

A :
The drive controller has detected a checksum error in the message received from the lift controller. The drive
controller ignores the message and sends a reply message with the following content:
• Status Byte: Contains the actual status of the drive controller with bit 7 set (error in the last message received)
• Process Data: Contains the actual extended status or the actual deceleration distance (which is 00 (Hex)in DCP3
mode)
B :
In the message from the lift controller to the drive controller, bit 7 (error in last reply message) is set in the
command byte. The current commands are processed normally. The drive controller repeats the last message sent.
Note:
If one of both devices is detecting a checksum error in a message when also bit 7 (error in last message) is set, this bit must be ignored
by the receiving device. In DCP4 mode, the drive controller's use of remaining distance message simplifies the behavior:
• The lift controller always sends the current command byte and the remaining distance
• The drive controller always replies with the current status byte
• In the event of transmission errors, only the last communication byte sent is repeated

Basic DCP Serial Communication Parameters

Interface
RS485 is used as physical layer. Transmission from the lift controller to the drive controller is serial and
asynchronous.
• Baud rate: 38,400 Baud
• Data bits: 8
• Parity: none
• Stop bits: 1
Timing
Since a half-duplex interface is used, the corresponding line drivers must be switched on or off dependent on the
transmission direction. To avoid collisions, the following timing has to be followed:
• Maximum Tx transmission driver switch-off time: 0.5 ms after the last bit was sent
• Maximum time delay for responding to a lift controller message: 10 ms after the last bit was received
• Lift controller message transmission start: 0 ms
• Latest time for switching off lift controller's Tx driver / Earliest time for drive controller transmission start:
2.0624 ms
• Latest drive controller transmission start: 11.5625 ms
• Latest time for switching off drive controller Tx driver / Earliest start for sending next lift controller message:
13.625 ms
• This leads to a transfer cycle of: 15 ms