Table 2. AC power specifications (continued)
Requirement
Power factor
Heat dissipation (operating maximum)
In-rush current
Startup surge current
AC protection
AC inlet type
Ride-through time
Current sharing

Dimensions and weight

Table 3. Dimensions and weight
Dimensions
Height: 3.40 in (8.64 cm)
Width: 17.50 in (44.45 cm)
Depth: 30.5" in (77.5 cm)
Note: The weight does not include mounting rails. Allow 2.3-4.5 kg (5-10 lb) for a rail set. The weights listed in this table do
not describe enclosures with solid state disk drives with Flash memory (called Flash or SSD drives). These Flash drive modules
weigh 20.8 ounces (1.3 lb) each.
Description
0.98 min at full load, low voltage
6
1.69 x 10
J/hr (1604 Btu/hr) max
37.6 A max for ½ line cycle "cold," per line cord at 240 V ac
38 A max for ½ line cycle "hot," per line cord at 240 V ac
29 A max, prior to HVDC regulation, during startup or after AC interruption
Flex Optimus, 16 A fuse on the line side of each power supply, both phases
Acbel Optimus, 15A fuse on the line side of each power supply, both phases
IEC320-C14 appliance coupler, per power supply
12 ms min
± 5% of full load, between power supplies
Vertical size
2 NEMA units
Weight (see note)
80lbs (36.3 kg)