Chapter 1: Specifications; Shipping And Storage Requirements; Power Requirements - Dell Data Domain DD6300 Manual

Hide thumbs Also See for Data Domain DD6300:
Table of Contents

Advertisement

This chapter contains the following topics:
Topics:

Shipping and storage requirements

Power requirements

Dimensions and weight
Shipping and storage requirements
NOTE:
Systems and components must not experience changes in temperature and humidity that are likely to cause
condensation to form on or in that system or component. Do not exceed the shipping and storage temperature gradient of
45°F/hr (25°C/hr).
Table 1. Shipping and storage requirements
Requirement
Ambient temperature
Temperature gradient
Relative humidity
Elevation
Power requirements
The input current, power (VA), and dissipation per enclosure listed in this document are based on measurements of fully
configured enclosures under worst-case operating conditions. Use the operating maximum values to plan the configuration of
your storage system. These values represent either:
● values for a single power supply line cord, or
● the sum of the values shared by the line cords of the combined power supplies in the same enclosure, with the division
between the line cords and supplies at the current sharing ratio (approximately 50% each).
A power and weight calculator is available at https://powercalculator.emc.com. Use this calculator to refine the power and heat
values to more-closely match the hardware configuration for your system.
A failure of one of the combined power supplies per enclosure results in the remaining power supply supporting the full load. You
must use a rackmount cabinet or rack with appropriate power distribution, and have main branch AC distribution that can handle
these values for each enclosure in the cabinet.
Table 2. AC power specifications
Requirement
AC line voltage
AC line current (operating maximum)
Power consumption (operating maximum)
6
Specifications
Description
50° F to 95°F (10°C to 35°C)
77°F/hr (25°C/hr)
20% to 80% noncondensing
0 to 10,000 ft (0 to 3,048 m), operation
is derated 1.1°C/1,000 feet (305 m) above
7,500 feet (2,286 m)
Description
100 to 240 V ac ± 10%, 47–63 Hz, single phase
8.4 A max at 100 V ac
4.4 A max at 200 V ac
1,105 VA (999 W) max