Trane Liquid-Cooled Adaptive Frequency AFDE Installation, Operation And Maintenance Manual page 45

Drive with tracer adaptiview control
Table of Contents

Advertisement

Table 11. Tracer TU: Configuration view: Starter Expanding section
Configuration of Drive
Note: These items are factory set, and checked at unit commissioning. Do not change without authorization
Description
Surge Protection
Surge Sensitivity
Power Loss Reset Time
Unit Line Voltage
Unit Motor Voltage
Motor NP FLA (TVA)
Motor NP RLA
Motor NP Power
Motor NP Hertz
Motor NP RPM
Stator Resistance
Flux Current Ref.
Acceleration Time
Deceleration Time
Starter Current Limit
Current Limit Gain
Power Loss Mode
Power Loss Time
Flying Start
Flying Start Gain
Use Trane Defaults
RTD Type
Line Side Items
(a) Use only the factory settings for this application as they are specific to the sales order. Instability and faults may occur by using other settings and is
not recommended. Contact your local Trane Representative for service when necessary.
AFDE-SVU02F-EN
Range
Default
0 = disable
1
1 = enable
0–100
20
0–255
60
(a)
180–8,000
180–15,000
(a)
0–2,000
(a)
1–2,000
(a)
0–4,000
(a)
5–250
(a)
60–24,000
(a)
0–10,000,000
(a)
0–1,200
(a)
1–99
10
1–99
30
1–3,200
1
(1.2XNMRA)(a)
0–5,000
10
decel, coast
decel
0–25
0
0 = disable
0
1 = enable
0-32,767
2,000
No
Yes
Yes
75 ohm at 75°F
75 ohm
100 ohm at 0°C
0 = Not Installed
0
1 = Installed
Service Interface
Units
Notes
%
Seconds
Use the default
Vac
Nameplate Data
Vac
Nameplate Data
Amps
Nameplate Data
Amps
Nameplate Data
kW
Nameplate Data
Hz
Nameplate Data
RPM
Nameplate Data
micro-ohms
Nameplate Data
Amps
Nameplate Data
Seconds
Seconds
Amps
Nameplate Data
Seconds
Default is 0; if you encounter AFD
power loss try 5 sec.
Enabled is not recommended.
Yes = required for most
applications.
No = allows "non-Trane"
application defaults to be used for
all other drive parameters not
accessible via the Tracer TU
service tool.
45