Trane Liquid-Cooled Adaptive Frequency AFDE Installation, Operation And Maintenance Manual page 44

Drive with tracer adaptiview control
Table of Contents

Advertisement

Service Interface
Table 8.
Tracer TU: Service Setpoints view: Adjustable Frequency Drive Setpoints section
Description
AF Control
Re-Optimization Sensitivity
Notes:
1. Use only Factory Defaults. Defaults other than above may effect chiller reliability
2. AF Re-optimization Sensitivity - Every 30 minutes the optimizing algorithm compares the current value of the inlet
guide vane position to the value that was stored after the last re-optimization. If the difference is greater than the AF Re
optimization Sensitivity setting, re-optimization occurs. This value is adjustable from 0 to 100%, where 0 would
guarantee re-optimization every 30 minutes and 100% would guarantee no re-optimization.
Table 9.
Tracer TU: Field Startup view: Adjustable Frequency Drive section
Description
Maximum Frequency
Minimum Frequency
AFD Surge Capacity Increase
Table 10. Tracer TU: Unit Status overrides
There is no specific view for overrides. If an item is available for override, the Override icon displays.
Frequency Command
44
Min
Max
Factory Default
N/A
N/A
(Auto, Fixed) Auto
0
100
20%
Min
Max
Factory Default
38
60
60
38
60
38
0
5
1
AFD Frequency:
When Manual is selected, the user can enter AFD Frequency commands
Units
N/A
Percent
Units
Hertz (Hz)
Hertz (Hz)
Hertz (Hz)
AFDE-SVU02F-EN