Considerations; Setting The Unit - Vertical - Trane TAMXA0A24V21DA Installer's Manual

Link communicating / variable speed outdoor compatible convertible air handler
Table of Contents

Advertisement

Setting the Unit — Vertical Installation
Table 6. Considerations
Provide a minimum height of 14 inches for proper unrestricted airflow
below the unit. Allow a minimum of 21 inches clearance in front of the
air handler to permit maintenance and removal of filter.
Position unit on suitable foundation. If a manufacturer approved
accessory is not used, a frame strong enough to support the total
weight of the unit, accessories, and duct work must be provided.
Isolate unit from the foundation using a suitable isolating
material.
Note: The following sound insulation kits are available to lessen
objectionable sound.
BAYINSKT175A for use with 17.5" cabinets
BAYINSKT215A for use with 21.5" cabinets
BAYINSKT235A for use with 23.5" cabinets
Table 7. Upflow Installation
TASB Installation
1.
Install the TASB plenum stand with integrated sound baffle using
the TASB instructions.
Note: Kit is used for open air applications.
TASB175SB for use with 17.5" cabinets
TASB215SB for use with 21.5" cabinets
TASB235SB for use with 23.5" cabinets
MITISRKIT1620 — Side return kit with 16" x 20" filter
Contact your distributor for more information.
Note: The following sound insulation kits are available to lessen
objectionable sound.
BAYINSKT175A for use with 17.5" cabinets
BAYINSKT215A for use with 21.5" cabinets
BAYINSKT235A for use with 23.5" cabinets
18-GJ89D1-1D-EN
Typical Closet Installation
Airflow
Typical TASB Installation
Airflow
19

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents