Optional Ultra Low Front Drip Piping Arrangements - Hussmann D5X-ULEP Installation And Service Manual

Ultra low front rear load medium temperature dairy merchandisers
Hide thumbs Also See for D5X-ULEP:
Table of Contents

Advertisement

D
P
3-2
RIP
5. Provide a suitable air break between
flood rim of the floor drain and outlet of
drip pipe. To meet code on low base
merchandisers, it may be necessary
to install a field-supplied drip pipe
reducer. An alternative is to cut the
last section of drip pipe at an angle.
Drip piping must be per case and connect below
floor level for Ultra Low Front models.
It is the installing contractor's responsibility to
consult local agencies for local code requirements.
Bottom of Case
Slope
Optional Excel Ultra Low Front Drip Piping Arrangements
P/N 0501930_A
S
IPING AND
PLASHGUARDS
IMPORTANT
ONE FLOOR DRAIN IS
REQUIRED FOR EACH CASE
Bottom of Case
Slope
Always Slope Toward Floor Drain
6. Prevent drip pipes from freezing:
a. Do NOT install drip pipes in contact with
uninsulated suction lines. Suction lines should
be insulated with a nonabsorbent insulation
material.
b. Where drip pipes are located in dead air
spaces, such as between merchandisers or
between a merchandiser and a store wall,
provide means to prevent freezing.
Bottom of Case
Slope
Slope
.
.
WWW
HUSSMANN
COM