Brazing; Removal And Replacement Of Compressor - Hoshizaki KML-200MAE Service Manual

Modular crescent cuber
Hide thumbs Also See for KML-200MAE:
Table of Contents

Advertisement

2. BRAZING

1. Refrigerant R22 itself is not flammable, explosive or poisonous. How-
ever, when exposed to an open flame, R22 creates Phosgene gas,
hazardous in large amounts.
2. Always recover the refrigerant and store it in an approved container. Do
not discharge the refrigerant into the atmosphere.
3. Do not use silver alloy or copper alloy containing Arsenic.
Note: All brazing-connections in the Evaporator Case are clear-paint coated.
Sandpaper the brazing-connections before unbrazing the components. Use a
good abrasive cloth to remove paint.

3. REMOVAL AND REPLACEMENT OF COMPRESSOR

Always install a new Drier every time the sealed refrigeration system is
opened. Do not replace the Drier until after all other repair or replacement
has been made.
Note: When replacing a Compressor with a defective winding, be sure to install the Start
Capacitor, Run Capacitor and Start Relay supplied with the replacement
Compressor.
1) Turn off the power supply.
2) Remove the panels.
3) Recover the refrigerant and store it in an approved container.
4) Remove the terminal Cover on the Compressor, and disconnect the Compressor
Wiring.
5) Remove the Discharge and Suction Pipes using brazing equipment.
6) Remove the Hold-down Bolts, Washers and Rubber Grommets.
WARNING
IMPORTANT