3.5

SFP Modules for Ethernet Ports

Refer to Chapter 2 of the PACSystems RX3i PROFINET Controller User Manual, GFK-2571.
3.6

External Switch VLAN Priority Settings

Refer to Chapter 4 of the PACSystems RX3i PROFINET Controller User Manual, GFK-2571.
3.7
Installing the USB Port Driver (revision –Axxx
only)
The USB port is only used for firmware updates. USB driver files are provided as part of
upgrade packages compatible with the PNS.
With the provided installation files accessible on either a local or network drive, connect the
computer's USB port to the USB port on the PNS module to be upgraded. When requested,
direct the installation to the proper location of the installation files.
The serial port name is COM followed by the next available number from 1 to 256. After the
computer assigns the USB port a COM port number, that computer uses the same COM port
number each time it connects to that PNS module.
Note:
3.8

Firmware Updates

Rev. -Axxx:
Note:
The PNS enters firmware update mode when commanded to do so from the WinLoader
update utility, or if a firmware component is corrupted or invalid. In firmware update mode,
Installation
Connect network cabling to the replacement PNS module.
Apply power to the replacement PNS module hardware.
Using the utility PROFINET DCP click on the Refresh Device List command button.
Highlight the row representing the newly installed PNS.
Click on the Edit Device command button and type in the Device Name.
When connecting the USB cable to the PNS, you may receive a warning for installing a driver
that has not passed Windows Logo testing. This warning should be ignored. Because each PNS
has a different serial number, the operating system recognizes each driver installation as
different.
The RX3i PNS does not prevent initiation of firmware update when it is actively connected to an
I/O Controller. When the PNS enters firmware update mode, the PNS and its modules go to their
I/O default modes. During the update, the PNS does not drive module outputs or send inputs to
the I/O Controller. When the firmware update is completed and the PNS is rebooted, its previous
connections are re-established and control resumes. Refer to section 2.1.8.6 Power-up LED
Patterns.
Section 3
Jul 2022
38