Graco XM PFP 273231 Repair And Parts Manual page 28

55 gallon (208 liter) feed system
Table of Contents

Advertisement

Repair
4. Set FULL CAL to 0.418 meters.
a. Press + to get to FULL CAL, then press E.
b. Press + until decimal point (.) appears, then
press E.
c. Press + until 4 appears, then press E.
d. Press + until 1 appears, then press E.
e. Press + until 8 appears, then press E.
f.
Press and hold E until the hourglass appears,
then release.
5. Map EMPTY TANK.
a. Press + to get to MAPPING, then press E.
b. Press E to get to CONFIRM DISTANCE.
c. Press + until TANK EMPTY appears, then
press E.
d. Press + under the check mark to confirm, END
OF SEQUENCE will appear. Press and hold E
until the hourglass appears, then release.
e. You are now finished. Press + and - together
until the hourglass appears, then release.
28
6. The transmitter display should show nothing in the
tank. Check the level display on the PFP machine
control. It should also show the tank as empty.
7. These settings can now be locked from display
control so they will not be inadvertently changed.
8. Set display to lock ON:
a. Turn display counter-clockwise to release it as
shown below (2).
b. Set the dip switch to the lock position as shown
below (3).
c. Replace display (4).
d. Replace screw on lid (5).
e. Engage cover securing clamp.
3A8047B