Install Power Supplies And Hardware; Install 1A2 Power Supply-Ch530 If Not Already Present; Install 1A2 Power Supply - Ch531 Prebuilt Panels - Trane Symbio 800 Control Upgrade Kit Installation Instructions Manual

For tracer ch530/ch531 dynaview display
Table of Contents

Advertisement

Install Power Supplies and
Hardware
Install 1A2 Power Supply—CH530 If Not
Already Present
Note: Proceed directly to the next stage of the installation
process:
for CH531 applications, or
If there are already two power supplies (1A1 and
1A2) in place from the previous CH530 control
system.
1. Find the factory-drilled mounting holes on the inner
back wall of the control panel enclosure to the right of
the existing power supply.
2. Attach the power supply to the mounting bracket with
the hardware provided.
3. Attach the power supply assembly to the back wall of
the enclosure using the 10-32 x 0.50-inch screws
provided.
Note: In all subsequent manual pages, this new power
supply will be referred to as the 1A2 power supply,
while the preexisting power supply from the
original control system will be referred to as the
1A1 power supply.
Figure 23. Installation of second power supply
CDUB-SVN001B-EN
Install 1A2 Power Supply - CH531 Prebuilt
Panels
1. Locate and remove the vent line solenoid time delay
relay and base.
Note: Do not unwire the base. The wires should be
long enough to reach the new location. Use
caution when removing the timer because the
center alignment post is very fragile.
2. Locate and remove the 1A1 power supply LLID and
bracket.
Note: Do not unwire the 1A1 power supply LLID. The
wires should be long enough to reach the new
location.
3. Locate and remove the middle back panel securing
screw on the right side.
4. Install the new sub back panel provided with the kit.
a. Secure the left side of the bracket using two #10-32
by 1/2-inch screws and the holes emptied by the
removal of the power supply bracket.
b. Secure the right side of the bracket using one 10-32
x 1.00-inch screw and the hole emptied by the
removal of the back panel securing screw.
5. Using the screws that were removed in
the existing power supply LLID onto the new panel in
the holes labeled 1A1.
6. Using the screws that were removed in
the vent line solenoid time delay relay and base in the
holes labeled 1K20.
Important:
The timer must be aligned correctly with the
base.
7. With the hardware provided, attach the new power
supply to the mounting bracket.
8. Using 10-32 x 0.50-inch screws provided, attach the
power supply assembly to the new panel in the holes
labeled 1A2.
Note: In all subsequent manual pages, this new power
supply will be referred to as the 1A2 power supply,
while the preexisting power supply from the
original control system will be referred to as the
1A1 power supply.
Installation
Step
2, attach
Step
1, attach
15