[901] Installer Walk Test Enable/Dis-
able
When this mode is ON, all zones become 24-Hr non force-armable
zones that will sound the bell (steady or pulsed ) for 2 seconds and
transmit their programmed alarm reporting codes (section [320-
323]) when violated. If the user attempts to arm while in Walk Test
the keypad will sound an error.
Fire Troubles are not supported in Walk Test.
Alarm Memory is cleared upon entering Walk Test.
To Enable Walk Test Mode:
Disable 'Keypad Blanking' - section [016] option 3
Disable 'Fire Bell is Continuous' - section[016] option 8
Enter from normal state:
[*] [8] [Install Code] [2] [901]
To Disable Walk Test Mode:
Re-enter:[*] [8] [Install Code] [2] [901]
Re-enable 'Keypad Blanking' and 'Fire Bell Continuous' if
required.
The User Walk Test ([*][6][8]) performs the same functions
as indicated here except that reporting codes are not trans-
mitted to the central station.

[902] Reset Module Supervision

All modules will automatically enroll within one minute upon
power-up. If modules are removed, enter this section to clear
any supervisory troubles that may be present. When this
mode is entered the system will attempt to re-enroll all
modules.
When this section is entered, all pending Supervisory Trouble
Restorals will not be logged or transmitted.
If a module is NOT communicating properly with the system,
it will be deleted when you enter this section.
To Reset Module Supervision:
Enter from normal state:
[*] [8] [Install Code] [2] [902]

[903] Module Supervision Field

When this section is entered, the system will display all mod-
ules enrolled on the system.
[*] [8] [Install Code] [2] [903]

[904] Device Placement Test

Device Selection - When this section is entered, a two digit entry is
required to select the zone number to be tested (01-32). If a device
is selected that is not enrolled, an error tone will sound.
Placement Indication - After the zone is selected the device sends
a signal to the NT9005 to register a signal strength value. These
results are indicated in the following table.
46
[*]
Function
RF Jam Detection - For proper RF Jam detction, zones must be
placement tested in the location that they will be used. A zone must
register 3 'Good' results in sequence for a successful test. After a
successful test the siren will sound for 2 seconds to indicate a suc-
cessful placement.

[990] Installer Lockout Enable

When enabled, the panel will sound an audible indication on power-
up (the phone relay will click 10 times). This feature will have no
effect on a software default (all programming will return to the fac-
tory defaults). If a hardware default is attempted while lockout is
enabled, the default will not occur and the attempt will be logged to
the event buffer.

[991] Installer Lockout Disable

Disables the feature described above.

[996] Restore Wireless Default Programming

When enabled, all programming in the RF section [804] will be
restored to factory defaults.

[999] Restore Factory Default Programming

Hardware Restore: Factory default programming can be restored
by shorting terminals YI and G2 for 10 seconds during Power-up if
Installer Lockout (Sections [990],[991] is disabled.
Software Restore: When enabled, all programming in the NT9005
will be restored to factory defaults.
FLASH
firealarmresources.com
Indication
LCD
Good
Good
Bad
Bad
Not Enrolled
-
To Perform Module Placement Test
Enter from normal state:
[*] [8] [Install Code] [2] [904] [Zone]
Press [#] to cancel test.
To Enable Installer Lockout - Enter from normal state:
[*] [8] [Install Code] [2] [990] [Install Code] [990]
To Disable Installer Lockout - Enter from normal state:
[*] [8] [Install Code] [2] [991] [Install Code] [991]
To Restore RF Factory Defaults - Enter from normal state:
[*] [8] [Install Code] [2] [996] [Install Code] [996]
When this section is entered, the Module Supervision Field
will be reset. See section [903].
To Restore Factory Defaults - Enter from normal state:
[*] [8] [Install Code] [999] [Install Code] [999]
Bell/Buzzer
1 Beep/Squawk
3 Beep/Squawk