Pentair PENTEK INTELLIDRIVE PID2000-1123 Owner's Manual

Pentair PENTEK INTELLIDRIVE PID2000-1123 Owner's Manual

Hide thumbs Also See for PENTEK INTELLIDRIVE PID2000-1123:

Advertisement

Quick Links

INTELLIDRIVE
CONSTANT PRESSURE CONTROLLER
OWNER'S MANUAL
• INSTALLATION
• OPERATION
• PARTS
Should the installer or owner be unfamiliar with the correct installation
and/or operation of this type of equipment, please contact the distributor
or manufacturer for the correct advice before proceeding with the
installation or operation of this product.

Advertisement

Table of Contents
loading

Summary of Contents for Pentair PENTEK INTELLIDRIVE PID2000-1123

  • Page 1 INTELLIDRIVE ™ CONSTANT PRESSURE CONTROLLER OWNER’S MANUAL • INSTALLATION • OPERATION • PARTS Should the installer or owner be unfamiliar with the correct installation and/or operation of this type of equipment, please contact the distributor or manufacturer for the correct advice before proceeding with the installation or operation of this product.
  • Page 2: Table Of Contents

    SAFETY 2 TABLE OF CONTENTS Important Safety Instructions Page Risk of electrical shock if VFD is connected to the power wiring before hanging the box . Read the Owner’s Manual and related documentation Always hang the VFD box before connecting the wires to it. carefully before attempting to install or operate the PENTEK INTELLIDRIVE .
  • Page 3: Description

    DESCRIPTION DESCRIPTION Specifications/Ratings Transducer Keypad The PENTEK INTELLIDRIVE uses a 4-20mA, Input Voltage..1-Phase 230VAC Nominal (190–265VAC) The keypad programs the Drive, monitors the Each carton contains: Input Frequency............50/60Hz 0-668 kPa pressure transducer to control • PENTEK INTELLIDRIVE Variable Frequency Drive status of the pump, and displays faults if they Ambient Temperate Range......-20°...
  • Page 4: Installation

    (be sure to leave a gap). Motor P/N Motor Rating Maximum Cable Length in M Lower bottom of cover into place. Push cover evenly against backplate, eliminating the gap. Rate PENTAIR Volts See Figure 7. Current mm² mm² mm²...
  • Page 5 230V single phase input power. If percent of the lower setpoint of the two. incoming power does not match this, have a Winding Terminal Pentek Franklin/Pentair Encapsulated SAVA Some applications may require a different qualified electrician alter supply voltage to Start/Aux Black Brown percentage when determining the setpoint.
  • Page 6: Initial Startup

    INITIAL STARTUP INITIAL STARTUP Initial Startup and Programming Procedures Service Factor Amps 23. Pump out well (if necessary): Changing a Parameter Value Ensure that the cover is installed before To maximize pump performance, be sure to Direct pump’ s discharge to appropriate This procedure works for ANY parameter.
  • Page 7: Programming

    PROGRAMMING PROGRAMMING VALUE Keypad Lock - Password Setting the Pressure MENU UNIT OF PARAMETER DESCRIPTION SETTINGS MEASURE The password locks or unlocks the blue NOTICE Default pressure setting is 414 kPa. DEFAULT MIN. MAX. buttons on keypad. All PENTEK INTELLIDRIVE If this value is changed, adjust tank pressure Hour Format Hours...
  • Page 8 PROGRAMMING PROGRAMMING TABLE 9 (CONTINUED) TABLE 9 (CONTINUED) VALUE MENU OR UNIT OF VALUE PARAMETER DESCRIPTION MENU UNIT OF SUB MENU MEASURE PARAMETER DESCRIPTION DEFAULT SETTINGS MEASURE DEFAULT Excessive Main pressure setpoint used. Enables or disables Excessive Runtime Runtime Enabled Disabled Enabled 668 kPa Sets main system operational...
  • Page 9: I/O Connections

    I/O CONNECTIONS I/O CONNECTIONS TABLE 10 - I/O FUNCTION, CONNECTIONS, RATINGS The I/O terminals are located in the center of the wiring compartment, as shown previously LABEL FUNCTION CONNECTION RATING in Figure 9. The Digital Input connections (I1 and I2) are Positive connection for transducer Red transducer wire 24 Volt...
  • Page 10: Additional Information

    ADDITIONAL INFORMATION TROUBLESHOOTING* RS-485 Communications Repair Parts FAULT POSSIBLE CAUSES SOLUTION Shorted output Check for any shorts in motor cables. RS-485 is a US-based telecommunications NOTICE The PENTEK INTELLIDRIVE will not standard for binary serial communications operate Franklin Electric 2-wire motors. Over Current Locked rotor Check for debris in pump.
  • Page 11: Troubleshooting

    TROUBLESHOOTING (CONTINUED) TROUBLESHOOTING FAULT POSSIBLE CAUSES SOLUTION Drive Reset Procedure Check all transducer wires are securely connected or for Intermittent connection damaged cable insulation. Follow the keypress sequence shown below to test the Drive. Check for proper wiring of all transducer wires and verify Open Connection cable connector securely attached to transducer.
  • Page 12: Owner's Information

    OWNER’S INFORMATION PENTEK INTELLIDRIVE Model No. PENTEK INTELLIDRIVE Serial No. Pump Model No. Pump Serial No. Motor Model No. Motor Service Factor Amps: Pressure Tank Model No. Pressure Tank Serial No. Dealer/Installer: Installer Phone No. Date of Installation: Wire Lengths in (Meters): Circuit Breaker to Drive: PENTEK INTELLIDRIVE to Motor: Supply Voltage:...
  • Page 13 1-21 Monash Drive, Dandenong South, VIC 3175 Australia | 1300 137 344 | pentair.com.au Information contained here-in remains the property of Pentair under Australian copyright law. Any reproduction, display, publication, modification or distribution is strictly prohibited without the prior written permission from Pentair.