Common Specifications - Mitsubishi FR-F800-E Instruction Manual

Inverter for fans and pumps fr-f846-00023(0.75k) to 03610(160k)-e-l2
Table of Contents

Advertisement

6.2

Common specifications

Control method
Output frequency range
Frequency
Analog input
setting
resolution
Digital input
Frequency
Analog input
accuracy
Digital input
Voltage/frequency
characteristics
Induction
Starting
motor
torque
IPM motor
Torque boost
Acceleration/deceleration
time setting
DC injection brake
(induction motor)
Stall prevention operation
level
Frequency
Analog input
setting
Digital input
signal
Start signal
Input signals (twelve
terminals)
Pulse train input
Operational functions
Open collector output
(five terminals)
Relay output
(two terminals)
Pulse train output
(FM type)
Pulse train
output
(FM type)
For meter
Current output
(CA type)
Voltage output
Operating
Operation
status
panel
(FR-DU08)
Fault record
Protective
function
Protective/
warning
function
Warning
function
Soft-PWM control, high carrier frequency PWM control (selectable among V/F control (Optimum excitation control),
Advanced magnetic flux vector control (Advanced optimum excitation control) and PM motor control)
0.2 to 590 Hz (The upper-limit frequency is 400 Hz under Advanced magnetic flux vector control, and PM motor control.)
0.015 Hz/60 Hz (terminal 2, 4: 0 to 10 V/12 bits)
0.03 Hz/60 Hz (0 to 5 V/11 bits or 0 to 20 mA/approx. 11 bits for terminals 2 and 4, 0 to 10 V/12 bits for terminal 1)
0.06 Hz/60 Hz (0 to 5 V/11 bits for terminal 1)
0.01 Hz
Within 0.2% of the max. output frequency (25°C 10°C)
Within 0.01% of the set output frequency
Base frequency can be set from 0 to 590 Hz. Constant-torque/variable-torque pattern or adjustable 5 points V/F can be
selected.
120% 0.5 Hz (Advanced magnetic flux vector control)
50%
Manual torque boost
0 to 3600 s (acceleration and deceleration can be set individually), linear or S-pattern acceleration/deceleration mode,
backlash countermeasures acceleration/deceleration can be selected.
Operation frequency (0 to 120 Hz), operation time (0 to 10 s), operation voltage (0 to 30%) variable
Activation range of stall prevention operation (0 to 150%). Whether to use the stall prevention or not can be selected. (V/F
control, Advanced magnetic flux vector control)
Terminals 2 and 4: 0 to 10 V, 0 to 5 V, 4 to 20 mA (0 to 20 mA) are available.
Terminal 1: -10 to +10 V, -5 to 5 V are available.
Input using the setting dial of the operation panel or the parameter unit
Four-digit BCD or 16-bit binary (when used with option FR-A8AX)
Forward and reverse rotation or start signal automatic self-holding input (3-wire input) can be selected.
Low-speed operation command, Middle-speed operation command, High-speed operation command, Second function
selection, Terminal 4 input selection, Jog operation selection, Output stop, Start self-holding selection, Forward rotation
command, Reverse rotation command, Inverter reset
The input signal can be changed using Pr.178 to Pr.189 (input terminal function selection).
100k pulses/s
Maximum and minimum frequency settings, multi-speed operation, acceleration/deceleration pattern, thermal protection,
DC injection brake, starting frequency, JOG operation, output stop (MRS), stall prevention, regeneration avoidance,
increased magnetic excitation deceleration, DC feeding, frequency jump, rotation display, automatic restart after
instantaneous power failure, electronic bypass sequence, remote setting, retry function, carrier frequency selection, fast-
response current limit, forward/reverse rotation prevention, operation mode selection, slip compensation, speed smoothing
control, traverse, auto tuning, applied motor selection, RS-485 communication, Ethernet communication, PID control, PID
pre-charge function, cooling fan operation selection, stop selection (deceleration stop/coasting), power-failure deceleration
stop function, PLC function, life diagnosis, maintenance timer, current average monitor, multiple rating, test run, 24 V power
supply input for control circuit, safety stop function, self power management, BACnet communication, PID gain tuning,
cleaning, load characteristics storage, emergency drive
Inverter running, Up to frequency, Instantaneous power failure/undervoltage, Overload warning, Output frequency
detection, Fault
The output signal can be changed using Pr.190 to Pr.196 (output terminal function selection).
Fault codes of the inverter can be output (4 bits) from the open collector.
50k pulses/s
Max. 2.4 kHz: one terminal (output frequency)
The monitored item can be changed using Pr.54 FM/CA terminal function selection.
Max. 20 mADC: one terminal (output current)
The monitored item can be changed using Pr.54 FM/CA terminal function selection.
Max. 10 VDC: one terminal (output voltage)
The monitored item can be changed using Pr.158 AM terminal function selection.
Output frequency, output current, output voltage, frequency setting value
The monitored item can be changed using Pr.52 Operation panel main monitor selection.
Fault record is displayed when a fault occurs. Past 8 fault records and the conditions immediately before the fault (output
voltage/current/frequency/cumulative energization time/year/month/date/time) are saved.
Overcurrent trip during acceleration, Overcurrent trip during constant speed, Overcurrent trip during deceleration or stop,
Regenerative overvoltage trip during acceleration, Regenerative overvoltage trip during constant speed, Regenerative
overvoltage trip during deceleration or stop, Inverter overload trip (electronic thermal O/L relay function), Motor overload trip
(electronic thermal O/L relay function), Heat sink overheat, Instantaneous power failure, Undervoltage, Input phase loss
Stall prevention stop, Loss of synchronism detection
earth (ground) fault overcurrent, Output short circuit, Output phase loss, External thermal relay operation
operation
, Option fault, Communication option fault, User definition error by the PLC function, Parameter storage device

fault (control circuit board), PU disconnection, Retry count excess
RS-485 terminals power supply short circuit, 24 VDC power fault, Abnormal output current detection
circuit fault, Ethernet communication fault
Safety circuit fault, Abnormal internal temperature, Internal circuit fault, Overspeed occurrence
charge fault
, PID signal fault


Operation panel lock
, Password locked

prevention (overvoltage), Electronic thermal relay function pre-alarm, PU stop, Continuous operation during communication
fault, Parameter copy, Safety stop, Maintenance timer 1 to 3
operation, Fan alarm, Internal-circulation fan alarm, 24 V external power supply operation, Ethernet communication fault
, Upper limit fault detection, Lower limit fault detection, Output side

, CPU fault, Operation panel power supply short circuit/

, Communication fault (inverter), Analog input fault, USB communication fault,

, Parameter write error, Copy operation error, Stall prevention (overcurrent), Stall

, USB host error, Load fault warning, Emergency drive in

Common specifications
, PTC thermistor

, Inrush current limit

, 4 mA input fault
, Pre-

