Heat & Glo 6000C-IFT Installation Manual
Hide thumbs Also See for 6000C-IFT:
Table of Contents

Advertisement

Quick Links

INSTALLER: Leave this manual with party responsible for use and operation.
OWNER: Retain this manual for future reference.
NOTICE: DO NOT discard this manual!
Models:
This appliance may be installed as an OEM
installation in manufactured home (USA
only) or mobile home and must be installed
in accordance with the manufacturer's
instructions and the Manufactured Home
Construction and Safety Standard, Title 24
CFR, Part 3280 in the United States, or the
Standard for Installation in Mobile Homes,
CAN/CSA Z240 MH Series, in Canada.
This appliance is only for use with the type(s)
of gas indicated on the rating plate. This
appliance is not convertible for use with other
gases, unless a certified kit is used.
In the Commonwealth of Massachusetts installation must be
performed by a licensed plumber or gas fitter.
See Table of Contents for location of additional Commonwealth
of Massachusetts requirements.
Installation Manual
Installation and Appliance Setup
Heat & Glo • 6000C-IFT, 8000C-IFT Installation Manual • 2502-980 Rev. M • 3/21
WARNING:
FIRE OR EXPLOSION HAZARD
Failure to follow safety warnings exactly
could result in serious injury, death, or
property damage.
• DO NOT store or use gasoline or other flam-
mable vapors and liquids in the vicinity of this
or any other appliance.
• What to do if you smell gas
- DO NOT try to light any appliance.
- DO NOT touch any electrical switch. DO
NOT use any phone in your building.
- Leave the building immediately.
- Immediately call your gas supplier from
a neighbor's phone. Follow the gas sup-
plier's instructions.
- If you cannot reach your gas supplier, call
the fire department.
• Installation and service must be performed
by a qualified installer, service agency, or the
gas supplier.
DANGER
DO NOT TOUCH GLASS
NEVER ALLOW CHILDREN
A barrier designed to reduce the risk of
burns from the hot viewing glass is provided
with this appliance and must be installed for
the protection of children and other at-risk
individuals.
HOT GLASS WILL
CAUSE BURNS.
UNTIL COOLED.
TO TOUCH GLASS.
1

Advertisement

Table of Contents
loading

Summary of Contents for Heat & Glo 6000C-IFT

  • Page 1 In the Commonwealth of Massachusetts installation must be performed by a licensed plumber or gas fitter. See Table of Contents for location of additional Commonwealth of Massachusetts requirements. Heat & Glo • 6000C-IFT, 8000C-IFT Installation Manual • 2502-980 Rev. M • 3/21...
  • Page 2: Table Of Contents

    D. Installing the Non-combustible Board....42  = Contains updated information. Heat & Glo • 6000C-IFT, 8000C-IFT Installation Manual • 2502-980 Rev. M • 3/21...
  • Page 3: Installation Standard Work Checklist

    _____________________________________________________________________________________ _________________________________________________________________________________________________ _________________________________________________________________________________________________ Comments Communicated to party responsible ____________________ by ______________________on ___________ (Builder / Gen. Contractor/) (Installer) (Date)  = Contains updated information. 2502-982 11/17 Heat & Glo • 6000C-IFT, 8000C-IFT Installation Manual • 2502-980 Rev. M • 3/21...
  • Page 4: Product Specific And Important Safety Information

    Some local building codes require the use of tempered glass with permanent marking in such locations. Glass meeting this requirement is available from the factory. Please contact your dealer or distributor to order. Heat & Glo • 6000C-IFT, 8000C-IFT Installation Manual • 2502-980 Rev. M • 3/21...
  • Page 5: Non-Combustible Materials Specification

    State of California to cause cancer and reproductive harm. For more information go to: www. P65Warnings.ca.gov. Heat & Glo • 6000C-IFT, 8000C-IFT Installation Manual • 2502-980 Rev. M • 3/21...
  • Page 6: Requirements For The Commonwealth Of Massachusetts

    VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OB- of the installation. STRUCTIONS”. See Gas Connection section for additional Common- wealth of Massachusetts requirements. Heat & Glo • 6000C-IFT, 8000C-IFT Installation Manual • 2502-980 Rev. M • 3/21...
  • Page 7: Getting Started

    1/2 - 3/4 in. length, #6 or #8 Self-drilling screws Caulking material (300 ºF minimum continuous exposure rating) One 1/4 in. female connection (for optional fan). Heat & Glo • 6000C-IFT, 8000C-IFT Installation Manual • 2502-980 Rev. M • 3/21...
  • Page 8: Inspect Appliance And Components

    Call a qualified service technician to inspect the appliance and to replace any part of the control system and/or gas control which has been under water. Heat & Glo • 6000C-IFT, 8000C-IFT Installation Manual • 2502-980 Rev. M • 3/21...
  • Page 9: Framing And Clearances

    36-1/8 28-1/2 33-1/2 14-1/4 34-5/8 8-1/2 2-1/4 2-7/8 9-11/16 8-1/2 26-7/8 6 dia. 40-7/8 1038 39-7/8 1013 14-3/16 15-3/8 Figure 3.1 Appliance Dimensions - 6000C-IFT Models Heat & Glo • 6000C-IFT, 8000C-IFT Installation Manual • 2502-980 Rev. M • 3/21...
  • Page 10 11-11/16 35-1/2 43-1/8 1096 17-3/4 35-1/2 8-1/2 36-5/8 2-3/8 2-7/8 9-15/16 8-1/2 28-7/8 42-7/8 1089 41-7/8 1064 14-1/16 17-1/16 Figure 3.2 Appliance Dimensions - 8000C-IFT Models Heat & Glo • 6000C-IFT, 8000C-IFT Installation Manual • 2502-980 Rev. M • 3/21...
  • Page 11 1-1/4 7-11/16 32-7/8 34-1/8 6000 ARC-36 39-7/16 22-7/16 44-1/4 1-1/4 7-11/16 34-13/16 36-1/16 8000 ARC-42 1002 1124 Figure 3.3 Decorative Front Dimensions - Folio and Arcadia Heat & Glo • 6000C-IFT, 8000C-IFT Installation Manual • 2502-980 Rev. M • 3/21...
  • Page 12 1-1/2 7-7/8 32-7/8 34-1/8 6000 CHA-36 22-7/16 39-7/16 44-1/8 1-1/4 7-7/8 34-13/16 36-1/16 8000 CHA-42 1002 1121 Figure 3.4 Decorative Front Dimensions - Halston and Chateau Heat & Glo • 6000C-IFT, 8000C-IFT Installation Manual • 2502-980 Rev. M • 3/21...
  • Page 13 37-1/8 1-1/4 7-1/2 32-7/8 34-1/16 6000 GALLERIA-6 38-9/16 22-3/4 44-1/16 1-1/4 7-1/2 34-3/4 8000 GALLERIA-8 1121 Figure 3.5 Decorative Front Dimensions - Chateau Forge and Galleria Heat & Glo • 6000C-IFT, 8000C-IFT Installation Manual • 2502-980 Rev. M • 3/21...
  • Page 14 6-3/4 32-7/8 34-1/8 6000 FSI-36 34-3/8 25-3/16 44-3/16 1-1/4 6-3/4 34-13/16 36-1/16 8000 FSI-42 1122 Figure 3.6 Decorative Front Dimensions - Clean Face and Iron Age Heat & Glo • 6000C-IFT, 8000C-IFT Installation Manual • 2502-980 Rev. M • 3/21...
  • Page 15: Clearances To Combustibles

    See Section 10.B 6000 Mantel Projections 1295 1067 1829 1438 55-7/8 61-1/2 19-3/4 See Section 10.B 8000 Mantel Projections 1419 1245 2007 1562 Figure 3.7 Appliance Locations Heat & Glo • 6000C-IFT, 8000C-IFT Installation Manual • 2502-980 Rev. M • 3/21...
  • Page 16 * Adjust framing dimensions for interior sheathing (such as sheetrock) C** Add 12 inches for rear venting with one 90º elbow. Figure 3.8 Clearances to Combustibles Heat & Glo • 6000C-IFT, 8000C-IFT Installation Manual • 2502-980 Rev. M • 3/21...
  • Page 17: Constructing The Appliance Chase

    • The chase must be properly blocked to prevent blown insulation or other combustibles from entering and making contact with fireplace or chimney. • Failure to maintain airspace may cause overheating and a fire. Heat & Glo • 6000C-IFT, 8000C-IFT Installation Manual • 2502-980 Rev. M • 3/21...
  • Page 18: Termination Location And Vent Information

    Refer to local codes. H=Measure Horizontal Distances from H V=Measure Vertical Distances from V Figure 4.1 Minimum Height From Roof to Lowest Discharge Opening Figure 4.3 Heat & Glo • 6000C-IFT, 8000C-IFT Installation Manual • 2502-980 Rev. M • 3/21...
  • Page 19: Vent Terminal Clearances

    12 in. (305 mm)* two sides beneath the floor.) vinyl or composite overhang 42 in. (1067 mm) 42 in. (1067 mm) Figure 4.4 Minimum Clearances for Termination Heat & Glo • 6000C-IFT, 8000C-IFT Installation Manual • 2502-980 Rev. M • 3/21...
  • Page 20: Approved Pipe

    WARNING! Risk of Fire or Asphyxiation. This appli- ance requires a separate vent. DO NOT vent to a pipe serving a separate solid fuel burning appliance. Heat & Glo • 6000C-IFT, 8000C-IFT Installation Manual • 2502-980 Rev. M • 3/21...
  • Page 21: Use Of Elbows

    8-1/2 DVP24 DVP36 25-1/2 DVP48 1219 DVP6A 3 to 6 76 to 152 2-1/8-4-1/4 54-108 DVP12A 3 to 12 76 to 305 2-1/8-8-1/2 54-216 Figure 4.5 Heat & Glo • 6000C-IFT, 8000C-IFT Installation Manual • 2502-980 Rev. M • 3/21...
  • Page 22: Measuring Standards

    • Horizontal pipe installed level with no rise. MEASURE TO SHADED SURFACE (OUTSIDE MOUNTING SURFACE) Figure 4.7 Measure to Outside Mounting Surface Figure 4.8 Measure to Top of Last Section of Pipe Heat & Glo • 6000C-IFT, 8000C-IFT Installation Manual • 2502-980 Rev. M • 3/21...
  • Page 23: Vent Diagrams

    Example: DVP pipe 3 ft. min. vertical = 11 ft. max. horizontal SLP pipe 7 ft. min. vertical = 11 ft. max. horizontal 1/4 in. max. (6 mm) Figure 4.9 Heat & Glo • 6000C-IFT, 8000C-IFT Installation Manual • 2502-980 Rev. M • 3/21...
  • Page 24 7.6 m = 40 ft. (12.2 m) Maximum = 25 ft. (7.6 m) Maximum ELBOW HEAT SHIELD (Required when V = 2 ft. or less) Figure 4.10 Heat & Glo • 6000C-IFT, 8000C-IFT Installation Manual • 2502-980 Rev. M • 3/21...
  • Page 25 = 1 ft. (305 mm) Minimum = 40 ft. (12.2 m) Maximum = 20 ft. (6.0 m) Maximum = 1 ft. (305 mm) Minimum INSTALLED HORIZONTALLY Figure 4.11 Heat & Glo • 6000C-IFT, 8000C-IFT Installation Manual • 2502-980 Rev. M • 3/21...
  • Page 26 16 ft * 4.9 m* 3 ft. 914 mm 14 ft.* 4.3 m* = 20 ft. (6.1 m) Maximum = 40 ft. (12.2 m) Maximum Figure 4.12 Heat & Glo • 6000C-IFT, 8000C-IFT Installation Manual • 2502-980 Rev. M • 3/21...
  • Page 27 Propane Propane 4 ft. Restrictor Restrictor Restrictor 8 ft. Restrictor 15 ft. 20 ft. 25 ft. 30 ft. 35 ft. Figure 4.13 40 ft. Figure 4.15 Heat & Glo • 6000C-IFT, 8000C-IFT Installation Manual • 2502-980 Rev. M • 3/21...
  • Page 28 1.2 m 20 ft. 6.1 m = 50 ft. (15.2 m) Maximum *No specific restrictions on this value EXCEPT cannot exceed 50 ft (15.2 m) Figure 4.17 Heat & Glo • 6000C-IFT, 8000C-IFT Installation Manual • 2502-980 Rev. M • 3/21...
  • Page 29 = 20 ft. (6.1 m) Maximum = 40 ft. (12.2 m) Maximum * No specific restrictions on this value EXCEPT V cannot exceed 40 ft. (12.2 m). INSTALLED HORIZONTALLY Figure 4.18 Heat & Glo • 6000C-IFT, 8000C-IFT Installation Manual • 2502-980 Rev. M • 3/21...
  • Page 30 = 16 in. (406 mm) Maximum Figure 4.19 One 45º Elbow Do not use a 45º elbow in corner installations. Use two 90º elbows instead. Figure 4.20 Heat & Glo • 6000C-IFT, 8000C-IFT Installation Manual • 2502-980 Rev. M • 3/21...
  • Page 31 3.7 m 15 ft. 4.6 m = 40 ft. (12.2 m) Maximum = 3 ft. (914 mm) Maximum = 20 ft. (6.1 m) Maximum Figure 4.22 Heat & Glo • 6000C-IFT, 8000C-IFT Installation Manual • 2502-980 Rev. M • 3/21...
  • Page 32 3.7 m 8 ft. 2.4 m 15 ft. 4.6 m = 40 ft. (12.2 m) Maximum = 15 ft. (4.6 m) Maximum INSTALLED HORIZONTALLY Figure 4.24 Heat & Glo • 6000C-IFT, 8000C-IFT Installation Manual • 2502-980 Rev. M • 3/21...
  • Page 33 = 40 ft. (12.2 m) Maximum *No specific restrictions on this value EXCEPT cannot exceed 40 ft. (12.2 m) Maximum = 8 ft. (2.4 m) Maximum INSTALLED HORIZONTALLY Figure 4.26 Heat & Glo • 6000C-IFT, 8000C-IFT Installation Manual • 2502-980 Rev. M • 3/21...
  • Page 34 • Ensure all joints are properly engaged and the chimney is properly secured. Table 2 CLEARANCE TO COMBUSTIBLES REQUIREMENTS DV-46DVA-GCL 3 IN. Exhaust Vent Pipe 5 IN. Heat & Glo • 6000C-IFT, 8000C-IFT Installation Manual • 2502-980 Rev. M • 3/21...
  • Page 35 0 ft. 0 mm Minimum 10 ft. 3.05 m Minimum 40 ft. 12.2 m 2 ft. 610 mm Maximum 40 ft. 12.2 m Maximum Figure 4.29 Heat & Glo • 6000C-IFT, 8000C-IFT Installation Manual • 2502-980 Rev. M • 3/21...
  • Page 36: Vent Clearances And Framing

    Top: 2-1/2 in. (64 mm) Bottom: 1/2 in. (13 mm) Sides: 1 in. (25 mm) Figure 5.1 Horizontal Venting Clearances To Combustible Materials Heat & Glo • 6000C-IFT, 8000C-IFT Installation Manual • 2502-980 Rev. M • 3/21...
  • Page 37: Wall Penetration Framing/Firestops

    * Shows center of vent framing hole for top or rear venting. The center of the hole is one (1) in. (25 mm) above the center of the horizontal vent pipe. Figure 5.3 Wall Penetration Heat & Glo • 6000C-IFT, 8000C-IFT Installation Manual • 2502-980 Rev. M • 3/21...
  • Page 38: Ceiling Firestop/Floor Penetration Framing

    INSTALL ATTIC INSULATION SHIELDS BEFORE OR AFTER INSTALLATION OF VENT SYSTEM CEILING FIRESTOP CEILING FIRESTOP INSTALLED BELOW CEILING INSTALLED ABOVE CEILING Figure 5.5 Installing the Attic Shield Heat & Glo • 6000C-IFT, 8000C-IFT Installation Manual • 2502-980 Rev. M • 3/21...
  • Page 39: Appliance Preparation

    Figure 6.5 (Generic Fireplace Shown) Remove the insulation from the outer vent pipe. Figure 6.3 (Generic Fireplace Shown) Remove the seal cap. Heat & Glo • 6000C-IFT, 8000C-IFT Installation Manual • 2502-980 Rev. M • 3/21...
  • Page 40 Figure 6.10 (Generic Fireplace Shown) Discard the vent cap, remove and discard the insulation basket. Figure 6.8 (Generic Fireplace Shown) Cut the metal retaining band and fold the sides out. Heat & Glo • 6000C-IFT, 8000C-IFT Installation Manual • 2502-980 Rev. M • 3/21...
  • Page 41: Installing Optional Heat Management Systems

    (it will snap into place). Slide the insulation gasket onto the vent section, up against the appliance and over the tabs. Figure 6.12 Heat Management Knockout Locations Heat & Glo • 6000C-IFT, 8000C-IFT Installation Manual • 2502-980 Rev. M • 3/21...
  • Page 42: Securing And Leveling The Appliance

    HEADER HEADER Figure 6.15 Non-combustible Board Note: Diagonal dimensions (A) and (B) must be within 1/4 inch of each other. Figure 6.13 Positioning the Appliance Squarely Heat & Glo • 6000C-IFT, 8000C-IFT Installation Manual • 2502-980 Rev. M • 3/21...
  • Page 43: Venting And Chimneys

    If predrilling holes, DO NOT penetrate inner pipe. For 90º and 45º elbows that are changing the vent direction Figure 7.4 Seams INCORRECT Heat & Glo • 6000C-IFT, 8000C-IFT Installation Manual • 2502-980 Rev. M • 3/21...
  • Page 44: Assemble Vent Sections (Slp Only)

    Note: Align seams to engage pipe, • All unit collar, pipe, slip section, elbow and cap outer then rotate counterclockwise to lock flues shall be sealed. Figure 7.5 Adding Venting Components Heat & Glo • 6000C-IFT, 8000C-IFT Installation Manual • 2502-980 Rev. M • 3/21...
  • Page 45: Secure The Vent Sections

    Figure 7.10 Rotate Seams for Disassembly connection point to appliance. 120º Figure 7.11 Align and Disassemble Vent Sections Figure 7.8 Securing Vertical Pipe Sections 120º Figure 7.9 Securing Horizontal Pipe Sections Heat & Glo • 6000C-IFT, 8000C-IFT Installation Manual • 2502-980 Rev. M • 3/21...
  • Page 46: Vertical Termination Requirements

    • Tighten nut and make sure the collar is tight against the Figure 7.12 Minimum Height From Roof to Lowest Discharge pipe section. Opening • Caulk around the top of the storm collar. See Figure 7.15. Heat & Glo • 6000C-IFT, 8000C-IFT Installation Manual • 2502-980 Rev. M • 3/21...
  • Page 47: Horizontal Termination Requirements

    • Rest the small leg on the extended heat shield on top of the pipe section to properly space it from the pipe section. Figure 7.15 Figure 7.15 Important Notice: Heat shields may not be field constructed. Heat & Glo • 6000C-IFT, 8000C-IFT Installation Manual • 2502-980 Rev. M • 3/21...
  • Page 48 DVP-TRAP1 can adjust 1-1/2 in. (3-1/8 to 4-5/8 in.) DVP-TRAP2 can adjust 4 in. (5-3/8 to 9-3/8) DVP-HPC1 can adjust 2-1/8 in. (4-1/4 to 6-3/8) DVP-HPC2 can adjust 4-1/8 in. (6-3/8 to 10-1/2) Heat & Glo • 6000C-IFT, 8000C-IFT Installation Manual • 2502-980 Rev. M • 3/21...
  • Page 49: Electrical Information

    Verify proper operation after servicing. WARNING! Risk of Shock! Replace damaged wire with type 105º C rated wire. Wire must have high temperature insulation. Heat & Glo • 6000C-IFT, 8000C-IFT Installation Manual • 2502-980 Rev. M • 3/21...
  • Page 50: Wiring Requirements

    ELECTRONIC CONTROL MODULE RF MODULE (FOR USE WITH OPTIONAL REMOTE CONTROL) 6 PIN APPLIANCE 6V DC ON/OFF BATTERY PACK CONTROL Figure 8.3 IntelliFire Touch Wiring Diagram Heat & Glo • 6000C-IFT, 8000C-IFT Installation Manual • 2502-980 Rev. M • 3/21...
  • Page 51 (1/4 in. male) as shown. Figure 8.4 Junction Box Wired to Wall Switch Heat & Glo • 6000C-IFT, 8000C-IFT Installation Manual • 2502-980 Rev. M • 3/21...
  • Page 52: Gas Information

    4500 feet (1370 m). • If substituting for these components, please consult Check with your local gas utility to determine proper local codes for compliance. orifice size. Heat & Glo • 6000C-IFT, 8000C-IFT Installation Manual • 2502-980 Rev. M • 3/21...
  • Page 53: Air Shutter Setting

    NOTICE: If sooting occurs, provide more air by opening the air shutter. AIR SHUTTER WING NUT Figure 9.1 Air Shutter Air Shutter Settings Propane 1/4 in. 3/4 in. 6000 1/4 in. 3/4 in. 8000 Heat & Glo • 6000C-IFT, 8000C-IFT Installation Manual • 2502-980 Rev. M • 3/21...
  • Page 54: Finishing

    HIGH TEMPERATURE (300 ºF/ 149 ºC MIN.) TOP AND SIDE SEAL JOINT BOTTOM 1 INCH (SHADED AREA) MAY BE COVERED WITH COMBUSTIBLE OR NON-COMBUSTIBLE MATERIAL Figure 10.1 Facing Materials Heat & Glo • 6000C-IFT, 8000C-IFT Installation Manual • 2502-980 Rev. M • 3/21...
  • Page 55: Mantel And Wall Projections

    = 35-1/2 IN. (8000C) Note: Measurement is taken from top of the opening, NOT the top of the fireplace. Figure 10.4 Minimum Vertical and Maximum Horizontal Dimensions - Non-Combustible Heat & Glo • 6000C-IFT, 8000C-IFT Installation Manual • 2502-980 Rev. M • 3/21...
  • Page 56: Decorative Fronts

    0-6 inches max. 10.8 Overlap 1 inch or less 10.6 Iron Age Inside 1-6 inches max. 10.7 Figure 10.6 Finishing Material 1 Inch Thick or Less Heat & Glo • 6000C-IFT, 8000C-IFT Installation Manual • 2502-980 Rev. M • 3/21...
  • Page 57 36-5/16 34-7/16 DECORATIVE FRONT (Outside decorative front width) (Includes 1/8 in. opening each side of decorative front) Figure 10.7 Finishing Material Thickness Greater Than One Inch Heat & Glo • 6000C-IFT, 8000C-IFT Installation Manual • 2502-980 Rev. M • 3/21...
  • Page 58 NON-COMBUSTIBLE FINISHING MATERIAL FINISHING STRIPS DECORATIVE FRONT FINISHING MATERIAL FINISHING MATERIAL FINISHING STRIPS REMOVED Figure 10.8 Inside Fit (Folio / CF) Figure 10.9 Removing Finishing Strips. Heat & Glo • 6000C-IFT, 8000C-IFT Installation Manual • 2502-980 Rev. M • 3/21...
  • Page 59: Appliance Setup

    Remove the splatter guard before lighting the appliance. C. Clean the Appliance Clean/vacuum any sawdust that may have accumulated inside the firebox or underneath in the control cavity. Heat & Glo • 6000C-IFT, 8000C-IFT Installation Manual • 2502-980 Rev. M • 3/21...
  • Page 60: Burner Top Installation

    6000C-IFT and 8000C-IFT models. Install ei- ther the black glass refractory or brick refractory per instruc- tions included with the kit. Figure 11.5 Embers Overlapping Burner Port Holes (LP only). Heat & Glo • 6000C-IFT, 8000C-IFT Installation Manual • 2502-980 Rev. M • 3/21...
  • Page 61: Install The Log Assembly

    Log #2 with the horizontal grate bar and slide Log # 2 toward the left until it rests against the far left grate tine. Heat & Glo • 6000C-IFT, 8000C-IFT Installation Manual • 2502-980 Rev. M • 3/21...
  • Page 62 6 inches for fireplaces with refractory installed if logs are placed properly. The measurement will be 6-3/4 inches for fireplaces that do not have refractory installed if logs are placed properly. Figure 11 Heat & Glo • 6000C-IFT, 8000C-IFT Installation Manual • 2502-980 Rev. M • 3/21...
  • Page 63 After slot and tab have been fitted together, mate the groove located on the bottom of Log #2 with the horizontal grate bar and slide Log # 2 toward the left until it rests against the far left grate tine. Heat & Glo • 6000C-IFT, 8000C-IFT Installation Manual • 2502-980 Rev. M • 3/21...
  • Page 64 Figure 10. Set the other end of Log #6 on the flat area located on top of Log #4 (see Figure 9). Log #6 will also rest against center grate tine. When properly installed, Log #6 will rest securely on all 3 contact points, not allowing movement or shifting. Heat & Glo • 6000C-IFT, 8000C-IFT Installation Manual • 2502-980 Rev. M • 3/21...
  • Page 65: Intellifire Touch Control System Setup

    1. The RC400 remote will need to be paired to the ECM. 2. Follow the installation instructions provided with the IntelliFire Touch remote and/or accessory kit(s). Heat & Glo • 6000C-IFT, 8000C-IFT Installation Manual • 2502-980 Rev. M • 3/21...
  • Page 66: Reference Materials

    6 in. (152 mm) 14 IN. (356 MM) 12 IN. (305 MM) DVP-WS (Wall Shield Firestop) DVP-RDS ROOF DECK INSULATION SHIELD Figure 12.1 DVP Vent Components Heat & Glo • 6000C-IFT, 8000C-IFT Installation Manual • 2502-980 Rev. M • 3/21...
  • Page 67 117 mm Length 5-3/8 in. 9-3/8 in. DVP-TRAP Trap2 Horizontal Termination Cap 137 mm 238 mm DVP-TRAP2 DVP-TRAP1 DVP-TRAPK2 DVP-TRAPK1 DVP-HPC2 DVP-HPC1 Figure 12.2 DVP Vent Components Heat & Glo • 6000C-IFT, 8000C-IFT Installation Manual • 2502-980 Rev. M • 3/21...
  • Page 68 9-1/2 in. (352 mm) (241 mm) 26 in. 660 mm 14 in. (356 mm) DVP-HSM-B DRC-RADIUS Extended Heat Shield Cap Shield Figure 12.3 DVP Vent Components Heat & Glo • 6000C-IFT, 8000C-IFT Installation Manual • 2502-980 Rev. M • 3/21...
  • Page 69 213 mm 146 to 213 mm 3° 87° 15 in. (381 mm) 10-1/2 in. 267 mm 10-7/8 in. 276 mm DVP-HRC-SS DVP-HRC-ZC-SS Figure 12.4 DVP Vent Components Heat & Glo • 6000C-IFT, 8000C-IFT Installation Manual • 2502-980 Rev. M • 3/21...
  • Page 70 COAXIAL to COLINEAR VENTING LINK-DV30B 768-380A DV-46DVA-GCL Flex Liner Kit Stainless Steel Flex Pipe Coaxial/Colinear Appliance Connector (Required) DVP-2SL Adapter Figure 12.6 Coaxial to Colinear Vent Components Heat & Glo • 6000C-IFT, 8000C-IFT Installation Manual • 2502-980 Rev. M • 3/21...
  • Page 71 Option A: IFT-RC400 Option B: IFT-RC150 and IFT-ACM. These accessories are purchased separately from the PVV-SLP. Contact your dealer to order. Figure 12.7 PVV-SLP Vent Components Heat & Glo • 6000C-IFT, 8000C-IFT Installation Manual • 2502-980 Rev. M • 3/21...
  • Page 72 (424 mm) (346 mm) 424 mm 12-1/2 in. (318 mm) SLP-LPC SLP Low Profile Cap (Approved for use with PVI-SLP-B only) Figure 12.8 PVI-SLP-B Vent Components Heat & Glo • 6000C-IFT, 8000C-IFT Installation Manual • 2502-980 Rev. M • 3/21...
  • Page 73 60 FT PV Wire Harness PVI-WH60 80 FT PV Wire Harness PVI-WH80 100 FT PV Wire Harness PVI-WH100 PVLP-HS PVLP-BEK Heat Shield Brick Kit Figure 12.9 PVLP-SLP Vent Components Heat & Glo • 6000C-IFT, 8000C-IFT Installation Manual • 2502-980 Rev. M • 3/21...
  • Page 74 1-1/2 in. 12 in. 5-1/2 in. 220 mm 38 mm 305 mm 146 mm SLP-WS SLP-FS Wall Shield Firestop Ceiling Firestop Figure 12.10 SLP Series Vent Components Heat & Glo • 6000C-IFT, 8000C-IFT Installation Manual • 2502-980 Rev. M • 3/21...
  • Page 75 12-5/8 IN. (321 mm) DVP-HSM-B Extended Heat Shield 12-5/8 IN. 10-5/8 IN. (321 mm) (270 mm) SLP-RDS ROOF DECK INSULATION SHIELD Figure 12.11 SLP Series Vent Components Heat & Glo • 6000C-IFT, 8000C-IFT Installation Manual • 2502-980 Rev. M • 3/21...
  • Page 76 28-1/2 in. 4-1/8 in. 724 mm 105 mm 13-1/2 in. 4-3/4 in. 343 mm 121 mm SLK-SNKD Snorkel Termination Cap Figure 12.12 SLP Series Vent Components Heat & Glo • 6000C-IFT, 8000C-IFT Installation Manual • 2502-980 Rev. M • 3/21...
  • Page 77: Accessories

    Please contact your Heat & Glo dealer with any questions or concerns. For the location of your nearest Heat & Glo dealer, please visit www.heatnglo.com. Printed in U.S.A. - Copyright 2021 Heat & Glo • 6000C-IFT, 8000C-IFT Installation Manual • 2502-980 Rev. M • 3/21...